Electrical System

Section 6

 

 

Water Level Control Circuitry

WATER LEVEL PROBE LIGHT

The water level probe circuit can be monitored by watching the water level light. The water level light is on when water contacts the probe, and off when no water is in contact with the probe. The water level light functions any time power is applied to the ice machine, regardless of toggle switch position.

During the freeze cycle, the water level probe is set to maintain the proper water level above the water pump housing. The water level is not adjustable. If the water level is incorrect, check the water level probe position. Reposition or replace the probe as necessary.

WATER INLET VALVE SAFETY SHUT-OFF

In the event of a water level probe failure, this feature limits the water inlet valve to a 6-minute on time. Regardless of the water level probe input, the control board automatically shuts off the water inlet valve if it remains on for 6 continuous minutes.

FREEZE CYCLE CIRCUITRY

Manitowoc’s electronic sensing circuit does not rely on float switches or timers to maintain consistent water level control. During the freeze cycle, the water inlet valve energizes (turns on) and de-energizes (turns off) in conjunction with the water level probe located in the water trough.

During the first 45 seconds of the Freeze Cycle:

The water inlet valve is on when there is no water in contact with the water level probe.

The water inlet valve turns off after water contacts the water level probe for 3 continuous seconds.

The water inlet valve will cycle on and off as many times as needed to fill the water trough.

After 45 seconds into the Freeze Cycle:

The water inlet valve will cycle on, and then off one more time to refill the water trough. The water inlet valve is now off for the duration of the freeze sequence.

HARVEST CYCLE CIRCUITRY

The water level probe does not control the water inlet valve during the harvest cycle. During the harvest cycle water purge, the water inlet valve energizes and de- energizes strictly by time. The harvest water purge jumper may be set at 45 seconds (top and center terminals) or 0 seconds (center and bottom terminals). Set the harvest water purge to 0 seconds when reverse osmosis or deionized water is used. Use the factory setting of 45 seconds for all other types of water.

HARVEST WATER PURGE ADJUSTMENT

45SECOND JUMPER POSITION

0SECOND JUMPER POSITION

SV3139

SV3140

6-24

Part Number 80-1634-3

Image 62
Contents Service Manual Read These Before Proceeding Personal Injury PotentialTable of Contents Section Before Calling For Service Table of Contents Section Ice Machine OperationSection Maintenance Table of Contents Section Electrical System Section Refrigeration SystemTable of Contents Ice Cube Sizes How to Read a Model NumberModel Numbers Self-Contained Water-CooledGeneral Information Section Accessories Section General Information Model/Serial Number Location Model/Serial Number LocationWarranty Coverage Electrical and AuCS Dimensions Ice Machine DimensionsWidth, Depth, and Height Dimensions GeneralS1800M Water-Cooled Installation Instructions Section Location of Ice MachineIce Machine Heat of Rejection Series Heat of Rejection Ice Machine Air ConditioningMinimum Circuit Ampacity Section Installation Instructions Electrical ServiceVoltage Electrical RequirementsSelf Contained ICE Machine 208-230/3/60 For United Kingdom OnlySelf Contained ICE Machine 115/1/60 or 208-230/1/60 Self Contained ICE Machine 230/1/50Water Inlet Lines Cooling Tower ApplicationsWater Supply Drain ConnectionsWater Supply and Drain Line SIZING/CONNECTIONS Installation Instructions SectionTypical Water Supply Drain Installation CondenserSection Installation Instructions Installation Check List AuCS Automatic Cleaning System Potential Personal Injury SituationSection Ice Machine Operation Component IdentificationIce Machine Operation Section Sequence Of Operation Initial START-UP or START-UP After Automatic SHUT-OFFHarvest Safety TimersHarvest Sequence 5. Water Purge Automatic SHUT-OFF 7. Automatic Shut-OffICE Thickness Check Ice Machine Operation Section Operational ChecksWater Level Ice Thickness CheckWater Purge Adjustment Harvest Sequence Water PurgeIce Machine Operation Section This page Intentionally Left BlankWater-Cooled Condenser Water Regulating Valve Exterior CleaningIce Machine Inspection AlphaSan→Sachet Replacement Frequency Maintenance Section GuardianInstallation Sachet Replacement ProcedureModel Amount of Cleaner Section Maintenance Interior Cleaning and SanitizingCleaning Procedure StepSolution Type Water Mixed With Sanitizer Maintenance SectionSanitizing Procedure Removal of Parts for CLEANING/SANITIZING Solution Type Water Mixed WithIce Thickness Probe Removal Water CurtainWater Curtain Removal Ice Thickness Probe Water Distribution Tube Removal Water Distribution TubeWater Trough Water Pump Removal Water Level ProbeWater Pump Dump Valve Disassembly Water Dump ValveEvaporator Tray Removal Drain Line Check ValveWater Inlet Valve SELF-CONTAINED WATER-COOLED ICE Machines Maintenance Section Removal from Service/WinterizationPry Open the Water Regulating Valve AUCS→ Accessory Checklist Problem Possible Cause To CorrectBefore Calling For Service Section Safety Limit FeatureSELF-CONTAINED WATER-COOLED Models Energized Parts ChartsSection Electrical System Water Purge SELF-CONTAINED ModelsInitial Start-Up or Start-Up After Automatic Shut-Off Self-Contained Water PurgeSelf-Contained Refrigeration System Start-Up Refrigeration System Start Up 5 Seconds Toggle SwitchRefrigeration System START-UP PRE-CHILL Electrical System SectionFreeze Sequence Self-Contained Pre-Chill Self-Contained ModelsSelf-Contained Freeze Self-Contained Models Toggle Switch Bin Switch Control Board RelaysFreeze Harvest Sequence Harvest Self-Contained Automatic Shut-Off Automatic Shut-OffAutomatic SHUT-OFF Section Electrical System Wiring Diagrams Wiring Diagram LegendS1800 SELF-CONTAINED 1 Phase Control BoardS1800 SELF-CONTAINED 3 Phase BIN Switch SpecificationsCheck Procedure Main FuseContinuity Test SymptomsDiagnostic Aids Water Curtain Removal NotesCheck Motor Windings to Ground Compressor Electrical DiagnosticsCheck Resistance Ohm Values Determine if the Compressor is SeizedCompressor Start Sequence Ptcr DiagnosticsWhat is a PTCR? Model Automatic Shut-Off and Restart Troubleshooting PTCR’sWHY a Good Ptcr MAY Fail To Start the Compressor During Start-Up First .25 1.0 SecondsModel Manitowoc Cera-Mite Room Checking the PtcrManitowoc Ptcr Part NumberRelay Diagnosing Start ComponentsCapacitor Relay Operation CheckICE/OFF/CLEAN Toggle Switch Switch Setting Terminals Ohm ReadingElectronic Control Board Control Board Safety Limits InputsHOW the Probe Works Freeze Time LOCK-IN FeatureIce Thickness Probe Cleaning Harvest LightDiagnosing ICE Thickness Control Circuitry Monitoring of Harvest Light CorrectionWater Level Probe Light Water Inlet Valve Safety SHUT-OFFElectrical System Section Water Level Control Circuitry Freeze Cycle CircuitryWait until the freeze cycle starts Problem Water Trough Overfilling During Freeze CycleDiagnosing Water Level Control Circuitry On or OFF Step Check Self Contained 1 Phase with Terminal Board SELF-CONTAINED Water -COOLED Models Freeze Cycle Refrigeration SequenceRefrigeration System Section S1800 SELF-CONTAINED Tubing Schematic General ICE Production Check Before Beginning ServiceWeights are in pounds Times are in minutesPossible Problem Corrective Action INSTALLATION/VISUAL Inspection ChecklistWater System Checklist Normal Ice Formation ICE Formation PatternExtremely Thin at Evaporator Outlet Extremely Thin at Evaporator Inlet No Ice FormationAnalyzing Why Safety Limits May Stop the Ice Machine Safety LimitsSafety Limit Indication Safety Limit Notes Possible Cause Check/CorrectSection Refrigeration System Freeze Cycle Discharge Pressure Low Checklist ProcedureFreeze Cycle Discharge Pressure High Checklist Analyzing Discharge Pressure During Freeze or Harvest CycleStep Example Using SY1004A Model Ice Machine Analyzing Suction Pressure During Freeze CycleFreeze Cycle Suction Pressure High Checklist Freeze Cycle Suction Pressure Low ChecklistFindings Comments Harvest Valve Temperature Check GeneralHarvest Valve Analysis Discharge Line Temperature Analysis General Column 2 LOW CHARGE/TXV Starving Final AnalysisColumn 1 Harvest Valve Leaking Column 3 TXV FloodingRefrigeration System Operational Analysis Tables Models Dual Expansion Valve Ice Machine Model NumberHigh Pressure CUT-OUT Hpco Control Hour Ice Production S1800 SeriesSelf-Contained Water-Cooled Cycle Times Operating PressuresSELF-CONTAINED RECOVERY/EVACUATION ConnectionsSelf-Contained Charging Procedures Charging ConnectionsSystem Contamination CLEAN-UP Determining Severity Of ContaminationMild System Contamination Cleanup Procedure Severe System Contamination Cleanup ProcedureSection Refrigeration System 10. Using Pinch-Off Tool FILTER-DRIERS Drier End Part Model Connection Size Number48 oz Total System Refrigerant ChargesSeries Version Charge S1800M Refrigerant Definitions RecoverNew Product Specifications RecycleNew Refrigerant Recovered or Recycled RefrigerantRefrigerant RE-USE Policy Reclaimed RefrigerantHFC Refrigerant Questions and Answers This page Intentionally Left Blank Page Attend a Manitowoc Factory Service School