Fisher & Paykel OR36SDBGX installation instructions Manual Shut-off Valve fig, Pressure Regulator

Page 13

 

B

gas connection

2

All gas connections must be made according to national and local codes. This gas supply (service) line must be the same size or greater than the inlet line of the appliance. Sealant on all pipe joints must be resistant to te action of LP/Propane gas.

The range is equipped for the use with NATURAL gas. It is design-certified by CSA International for NATURAL and L.P. gases with appropriate conversion.

The model/serial rating plate, located on the inner side of the storage compartment pivoting panel, has information on the type of gas that can be used. If this information does not agree with the type of gas available, check with the local gas supplier. See page from 19 to 23 for L.P. gas conversion inctructions.

1. Manual Shut-off Valve (fig. 2.1):

A manual shut-off valve must be installed in an accessible location in the gas line external to the appliance for the purpose of turning on or shutting off gas to the appliance (In Massachusetts such shutoff devices should be approved by the Board of State Examiners of Plumbers & Gas Fitters). This valve should be located in the same room as the range and should be in a location that allows ease of opening and closing (in a position where it can be reached quickly in the event of an emergency).

Do not block access to the shutoff valve. The valve is for turning on or shutting off gas to the appliance.

Shutoff valve

“open” position

To range

Gas supply line

Fig. 2.1

Explosion Hazard

Use a new CSA or UL approved gas supply line.

Install a shut-off valve.

Securely tighten all gas connec- tions.

If connected to LP, have a quali- fied person make sure gas pres- sure does not exceed 14" water column.

Examples of a qualified person include licensed heating person- nel, authorized gas company per- sonnel, and authorized service personnel.

Failure to do so can result in death, explosion, or fire.

2. Pressure Regulator:

a)All heavy duty, commercial type cooking equipment must have a pressure regulator on the incoming service line for safe and efficient operation, since service pressure may fluctuate with local demand.

Before installing the regulator mount the 1/2” NPT (conical) male connector to the regulator (see picture 2.2a). Gasket supplied have to be placed between 1/2” NPT (conical) connector/extension pipe male pipe fitting (see picture 2.2b).

The regulator supplied with this range must be installed before any gas connections are made.

Use supplied pressure regulator only.

b)Assemble the extension pipe + pressure regulator group to the range manifold interposing the gasket supplied.

13

Image 13
Contents Installation instructions Instructions dinstallation ALL Ranges can TIP For Installer only Installation Instructions Electrical Grounding Instructions Replacement PartsProximity to Side Cabinets A1installationGAS and Electric Connection 500 500 Levelling the Cooker Fitting the Adjustable FeetMoving the Cooker Assembling the Backguard It is mandatory to installOr the Island Trim Backguard or the island trim455 ANTI-TIP Stability Device Installation InstructionsPressure Regulator Manual Shut-off Valve figPressure Regulator Installation Step Step Step Connector GAS Connection SpecificationFlexible Connections Leak TestingRigid Pipe Connections Conversion to LP/PROPANE GAS Setting the Pressure Regulator figInjectors Table Operations to be Performed When Substituting InjectorsRapid and triple ring burners Setting the Burner Minimum Valves may varyOven Burner Adjustment of the Oven Burner Minimum Recommended ground method Electrical connectionWiring Diagram Avertissement ’INTENTION DE L’INSTALLATEUR Seulement Instructions D’INSTALLATION Pièces DE Rechange Instructions DE Mise À LA TerreProximité DES Armoires Raccordements Électrique ET AU GAZ 0po Min Déplacement DE LA Cuisinière Installation DES Pieds RéglablesGarniture d’îlot est recommandée ’installation du dosseret ou de laMontage DU Dosseret OU DE LA Garniture D’ÎLOT455,5 26- 11/16 po 678 mm Régulateur de pression Robinet d’arrêt manuel figInstallation DU Régulateur DE Pression Étape Étape Étape Spécification DU Raccordement AU GAZ Raccords de tuyaux rigides Raccords flexiblesVérification de l’absence de fuite Réglage DU Régulateur DE Pression fig Conversion AU GAZ PROPANE/GPLBrûleurs Tableau DES InjecteursLes robinets peuvent varier Réglage Minimum DU BrûleurBrûleur du four Réglage Minimum DU Brûleur DU Four Raccordement électrique Méthode de mise à la terre recommandéeSchéma DE Câblage Page Page US CA