Unified Brands VENTILATION SYSTEMS specifications a. Fan Start

Page 16

started and stopped manually or programmed or automatic operation.

a. Fan Start

The exhaust and air make-up fans can be started manually by pressing "FAN ON/WASH OFF" on the PAWS panel. If the wash cycle is in progress it will stop immediately and the fans will start. The PAWS display will indicate "FAN ON/WASH OFF".

b. Fan Stop

The exhaust and air make-up fans can be stopped manually by pressing "FAN OFF/WASH OFF" on the PAWS panel. The fans will stop immediately. The PAWS display will indicate "FAN OFF/WASH OFF".

c. Wash Start

The wash cycle can be started manually by pressing "FAN OFF/WASH ON'' on the PAWS panel. If the fans are on, they will stop immediately. The display will indicate "WASH 1" and the total time [in hours and minutes] remaining until the wash cycle ends.

d. Wash Stop

The wash cycle can be stopped manually by pressing "FAN OFF/WASH OFF" on the PAWS panel. The wash cycle will stop immediately. The PAWS display will read "FAN OFF/WASH OFF".

2. Trouble Conditions

a. Low Detergent Indicator

If the detergent level drops below the bottom of the detergent probe, the PAWS panel horn will sound and the display will flash "DETERGENT LOW". The horn can be silenced by pressing the "VFC Horn Silence" switch, but the trouble condition will continue to be displayed. The detergent pump will not operate until the detergent tank is refilled. The fan and wash cycles will continue to operate normally, however, the display will continue to flash "LOW DETERGENT". When the detergent tank is refilled, the trouble condition will automatically clear itself after approximately 10 seconds.

b. Supervised Water Valve [optional]

If your PAWS panel is equipped with the optional supervised valve, the PAWS panel horn will sound and the display will flash

"PLENUM WASH AND FIRE CYCLES LOST" when the valve is closed. The horn can be

silenced by pressing the "VFC Horn Silence" switch, but the trouble condition will continue to be displayed. The fan will operate normally, hot water will not flow during the wash cycle and the display will continue to flash "PLENUM WASH AND FIRE CYCLES LOST". When the valve is opened, the alarm condition will automatically clear itself. In the event that the detergent level drops below the probe and the optional supervised valve is closed at the same time, the horn will sound and the display will alternate between "DETERGENT LOW" and

"PLENUM WASH AND FIRE CYCLES LOST". The horn can be silenced by pressing the "VFC Horn Silence " switch.

3. Hood Plenum Fire Protection a. Automatic Operation

In the event of a fire in and/or under the ventilator, the fans will turn off and the plenum wash will be activated when the temperature at the duct collar exceeds 300°F. The display will read "AUTO FIRE CYCLE FAN OFF/WASH ON" and the PAWS panel alarm will sound. The alarm cannot be silenced. When the temperature at the duct collar drops below 300 °F, the PAWS panel will enter the fire delay cycle. During the fire delay cycle the fan will remain off and the hood plenum wash will remain on for a programmable period of time then automatically return to normal operation. The fire delay cycle can be terminated by pressing "FAN OFF/WASH OFF" on the PAWS panel. [See Sec. 4.b.2.c for setting Fire Delay Cycle Duration].

b. Manual Operation

The PAWS panel may be equipped with the optional "Manual Fire Switch". Pulling the "Manual Fire Switch" will turn on the exhaust fan(s) and activate the plenum hood wash to act as a fire barrier. The display will read "MAN'L FIRE CYCLE FAN ON/WASH ON" and the PAWS panel alarm will sound. The alarm cannot be silenced. After the "Manual Fire Switch" is reset, the PAWS panel will enter the fire delay cycle. During the fire delay cycle the exhaust fan will remain on for a programmable period of time then automatically return to normal operation. The fire delay cycle can be terminated by pressing "FAN OFF/WASH OFF" on the PAWS panel. [See Sec. 4.3 for setting Fire Delay Cycle duration].

4.Programming Instructions [Refer to fig. 17A

&17B]

a. Setting the Clock

13

Image 16
Contents VENTILATION SYSTEMS OPERATORS MANUAL1055 Mendell Davis Drive Jackson, MS 888-994-7636,fax avtecind.comTABLE OF CONTENTS VENTILATOR FEATURES AND ACCESSORIES Air Adjustment BafflePERIODIC MAINTENANCE G. Fusible Link Replacement1I. TYPES OF SYSTEMS Installation shall be in accordance with NFPA NOTE Welds must not impede operation of damper Page Page Fig 8a Fig 8b 9.Terminal Block #11 TB-11has three 3 pairs of terminals. The first pair of terminals are low voltage connections for the detergent low level probe. The probe should be installed in the detergent container so that it does not protrude above the top of the detergent pump inlet strainer. fig. #9 This is intended to prevent cavitation of the pump and will advise when the tank needs to be refilled. The probe rods may be cut to facilitate a neat and effective installation Terminal Block Designation For authorized sevice techinician use onlyError! Not a valid link Page VI. OPERATION vac as long as the START Button is depressed a. Fan Start b. Setting the PAWS d. Reviewing The Daily Event Schedule OFF/WASH Page l. Detergent Pump and Tank Refer to fig E. Fire Dampers 1. Fusible Link Type fig. 3. Slot-TypeInternal Air Make-Up D. Grease Collection Receptacle A. PAWS PANEL - ELECTRICAL B. VCW PANEL - ELECTRICALC. PAWS/VCW PANEL - PLUMBING ITEM NOD. EVAC DETERGENT E. ELECTRO - MECHANICAL DAMPERITEM NO DESCRIPTIONF. FUSIBLE LINK DAMPER G. HOOD CANOPYITEM NO AVTEC PART NOCleaner/Degreaser Cleaner/DegreaserFor Exhaust Ventilator Auto-washCleaner UNIQUE, POWERFUL CLEANING FORMULAAIR MOVEMENT RECORDINGS Project NameA. ENERGY AIRE HOODS - EXHAUST B. FILTER HOODS - EXHAUSTPage EXHAUST CALCULATING AND RECORDING AIR MOVEMENTSUPPLY AVTEC SERVICE AGENCY, CALL OR WRITE TO FOR THE NAME AND LOCATION OF THE NEAREST