Unified Brands VENTILATION SYSTEMS specifications vac as long as the START Button is depressed

Page 15
vac as long as the "START" Button is depressed.

vac as long as the "START" Button is depressed.

d.Once the "Start" Button is released, power[120vac] will be present at terminals No. 2 & No. 6. If no power is present after releasing start button verify that the fan contactor has been wired as shown on VCW Panel Electrical Schematic.

e.Voltage present at terminals No. 2 & No. 6 after pushing "START" Button, fans won't operate. This condition indicates that the control wiring is operating properly, therefore the problem must be in the fan motor itself or the power supply wiring to fan thru the normally open contactor or the fan contactor.

b.Auto Wash Solenoid does not open. 1.Check that fuse is intact.

2.Check terminals No. 1 and No. 2 with volt meter.

a.If 120vac proceed to step 2d.

b.If no voltage, check fuse and wiring to panel.

c.Check panel circuit breaker and verify that it is "ON",

d.Press "Stop" button in completely and hold for one [1] full second.

e.Check terminals No. 3 and No. 4 with volt meter.

i.If 120vac is present, check wiring to water solenoid. Check voltage at solenoid coil. If 120vac is present, replace coil. If no voltage, refer to step 2.b.

ii.Check the timer relay inside the VCW Panel to verify that power is going thru the contacts and that the coil is engaging. If relay doesn't function properly, replace the relay, If relay functions properly proceed to step 4.

iii.Check wiring against schematic to verify that is correct. Check condition of wires and connections to verify that they are not loose or damaged.

c. Auto Wash Solenoid will not close. 1.Check terminals No. 3 & No. 4 for voltage

[120vac]. If no voltage is present proceed to step e.

2.Check the wiring to the fire switch pull station to see that it has been wired to the correct contacts.

3.Check the fire switch pull station [optional] to verify it has not been pulled.

4.Check all the dampers on the ventilator to verify that none of the dampers have been activated into the fire condition.

5.Check condition of solenoid for damage or debris.

d.Solenoid coil activates but no water flow is present.

1.Check water pressure gauge. If water pressure of 25 psig or more is present proceed to steps 2 & 3. If no water pressure is present proceed to steps 4 & 5.

2.Check solenoid valve for damage or debris.

3.Check for water line blockage and verify all spray nozzles are clear.

4.Check all water supply valves to verify they are open.

5.Check and clean all line wye strainers.

B. PAWS Control Panel [Refer to fig. 17] 1. Manual Operation

The Programmable Automatic Wash Sequence [PAWS] Panel is designed to control the operation of the ventilator exhaust and air make-up fans and wash the grease extraction plenum with a hot water/detergent solution. The fan operation and wash sequence can be

12

Image 15
Contents 888-994-7636,fax avtecind.com VENTILATION SYSTEMSOPERATORS MANUAL 1055 Mendell Davis Drive Jackson, MSTABLE OF CONTENTS G. Fusible Link Replacement VENTILATOR FEATURES AND ACCESSORIESAir Adjustment Baffle PERIODIC MAINTENANCE1I. TYPES OF SYSTEMS Installation shall be in accordance with NFPA NOTE Welds must not impede operation of damper Page Page Fig 8a Fig 8b 9.Terminal Block #11 TB-11has three 3 pairs of terminals. The first pair of terminals are low voltage connections for the detergent low level probe. The probe should be installed in the detergent container so that it does not protrude above the top of the detergent pump inlet strainer. fig. #9 This is intended to prevent cavitation of the pump and will advise when the tank needs to be refilled. The probe rods may be cut to facilitate a neat and effective installation For authorized sevice techinician use only Terminal Block DesignationError! Not a valid link Page VI. OPERATION vac as long as the START Button is depressed a. Fan Start b. Setting the PAWS d. Reviewing The Daily Event Schedule OFF/WASH Page l. Detergent Pump and Tank Refer to fig E. Fire Dampers 1. Fusible Link Type fig. 3. Slot-TypeInternal Air Make-Up D. Grease Collection Receptacle ITEM NO A. PAWS PANEL - ELECTRICALB. VCW PANEL - ELECTRICAL C. PAWS/VCW PANEL - PLUMBINGDESCRIPTION D. EVAC DETERGENTE. ELECTRO - MECHANICAL DAMPER ITEM NOAVTEC PART NO F. FUSIBLE LINK DAMPERG. HOOD CANOPY ITEM NOUNIQUE, POWERFUL CLEANING FORMULA Cleaner/DegreaserCleaner/Degreaser For Exhaust Ventilator Auto-washCleanerB. FILTER HOODS - EXHAUST AIR MOVEMENT RECORDINGSProject Name A. ENERGY AIRE HOODS - EXHAUSTPage CALCULATING AND RECORDING AIR MOVEMENT EXHAUSTSUPPLY FOR THE NAME AND LOCATION OF THE NEAREST AVTEC SERVICE AGENCY, CALL OR WRITE TO