D. Grease Collection Receptacle
Should be emptied at least once a day, and cleaned daily with a strong detergent.
E. Hood Canopy
1.Inside hood canopy should be wiped down as needed. The area at the exhaust intake openings should be wiped down daily.
2.Inspect inside of extraction chamber at least monthly, to insure proper cleaning and that the trough is free of foreign matter.
F.Detergent System
1.Detergent tank should be checked at least weekly; and cleaned every six months. Always keep cover on tight to prevent spillage and evaporation.
2.A colloid type detergent, is recommended due to its
3.All fittings should be checked for air tightness at least monthly.
4.Foot check valve should be cleaned every six months.
G.Fusible Link Replacement
1.Blade Type [Refer to fig. 27]
Exhaust damper fusible links are rated at 350°F [P/N AS LNK0302] and Air Make- up damper fusible links are rated at 286°F [P/N AS LNK0303]. Fusible links shall be replaced at least annually per NFPA 96, 8-
2.1.2.New "S" hooks [P/N FA HOK0301] should be used whenever the fusible links are replaced.
22
Cable tension can be adjusted by moving the
fig. 27
2.Curtain Type [Refer to fig. 28]
When
fig. 28