4.Terminal Block #2 [TB-2] has three [3] pairs of terminals and is located at the upper right corner of the Input/Output Board. The first pair of terminals are for the number one wash valve solenoid. This will be the only wash output active in a P-10-__ or P-15-__ Control Panel. The second pair of terminals are for the number two wash valve solenoid. The third pair of terminals are for the number three wash valve solenoid.
5.Terminal Block #3 [TB-3] has three [3] pairs of terminals. It will not be present on P-10-__ or P- 15-__ Control Panels. The first pair of terminals are for wash valve solenoid number four. The second pair of terminals are for the number five wash valve solenoid. The third pair of terminals are for the number six wash valve solenoid.
6.Terminal Block #4 [TB-4] has three [3] pairs of terminals. It will not be present on P-10-__ or P- 15-__ Control Panels. The first pair of terminals are for the number seven wash valve solenoid. The second pair of terminals are for the number eight wash valve solenoid.
7.Terminal Block #5 [TB-5] has three [3] pairs of terminals. The first pair provides power for the detergent pump. The second pair provides power for the PAWS Alarm/Trouble horn. [The third pair provides power for the vent fan contactors. [see figs. #8a & 8b]
Note that the maximum output is one-and-one- half [1-1/2] amperes. If the total inrush current for all contactors will exceed this limit, an intermediate relay must be used.
8.Terminal Block #9 [TB-9] has three [3] pairs of terminals and is located at the lower left corner of the Input/Output Board. The first pair of terminals are for connection to the optional supervised shut-off valve. If the panel is not equipped with this option, a jumper wire must be installed. The second pair of terminals are for connection to the Manual Fire Switch. The third pair of terminals are for connection to the automatic fire switch contacts terminals are for connection to the automatic fire switch contacts.