To adjust air intake slot, turn nuts to loosen, move air adjustment baffles up or down until the desired slot opening is obtained, and tighten nuts.
E. Fire Dampers
1. Fusible Link Type
Some ducts are protected by fire dampers which are activated by a fusible link rated at 360οF exhaust and 286οF supply When this temperature is exceeded, the fusible link melts allowing the fire damper to fall closed. This linkage should be inspected and the fusible links replaced annually. Fusible links in the exhaust duct collar are readily accessible by removing the baffle filters [Models AF] or grease extractor modules [Models AX]. [Refer to fig. 20 and 24] An access plate is provided for access [supply] duct collar for all models.
fig. 24
The damper can be manually closed by pulling down on the red knob at the end of the damper reset arm and allowing it to swing away from the plenum.
If the damper has been activated by excessive temperature, it cannot be reset until the temperature has dropped below 300ο
F.After the temperature has dropped below
300οF, the damper can be reset and opened by pushing the damper reset arm toward the plenum until it latches.
If the fusible link has melted, it must be replaced before the damper can be reset. An access plate is provided.
When the damper is closed manually or if the fusible link melts and causes the damper to close, the fan and auto wash down are not affected.
When the damper closes due to activation of the thermoswitch, the fan[s] will shut OFF and the auto wash will actuate.
F.Air
Ventilators may be supplied with four [4] different
1. Grill Registers [Refer to fig. 25]
Grill registers are located for external discharge or both internal and external discharge. Internal register have fixed louvers for proper "Short Cycle" of air. External registers have
FIRE DAMPER
register. The airflow may be adjusted by turning the damper adjustment screwhead located just behind the louvers as shown in fig. 25.
fig. 25
2.
The