4.0 - Installation and Start-Up
WARNING
THE UNIT MUST BE INSTALLED BY PERSONNEL WHO ARE QUALIFIED TO WORK WITH ELECTRICITY AND PLUMBING. IMPROPER INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND/OR DAMAGE TO THE EQUIPMENT. THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES.
CAUTION
DO NOT INSTALL THE UNIT WITH THE RIGHT SIDE VENTS BLOCKED OR WITHIN 30 CENTIMETERS OF A HEAT SOURCE (SUCH AS A BRAISING PAN, DEEP FRYER, CHAR BROILER, OR KETTLE).
TO AVOID DRAINAGE PROBLEMS, LEVEL THE UNIT FRONT TO BACK.
4.1Electrical Supply Connection
4.1.1Access for Connection
Panel Removal
Open the lower front panel by removing the screws from panel. Lift the panel, and swing its bottom toward you. Set the panel aside.
4.1.2Supply Voltage
The unit must be operated at the rated nameplate voltage, plus or minus 10 percent.
4.1.3Phase Selection
Refer to the schematic (Page 31) for wiring information.
CAUTION
THE UNIT MUST HAVE A SEPARATE EARTHING WIRE FOR SAFE OPERATION.
4.1.4Terminal Block
The terminal block for incoming power is located at the back of the control compartment.
The ground terminal is located in the wiring compartment next to the terminal block. The unit must have a separate ground wire for safe operation. The earthing wire must be of the same size as the supply wire.
4.1.5Supply wire
WARNING
TO AVOID DAMAGE OR PERSONAL INJURY, FOLLOW THE ELECTRICAL SCHEMATIC EXACTLY WHEN CONNECTING THE UNIT.
Determine the type of wire you need for the power supply, find the operating voltage and phase on the unit data plate, or use the table on the next page. The “Electrical Supply Connection” label inside the unit gives directions for proper connection of the terminal block jumpers. The knockout hole is sized for a 35 mm conduit fitting.