Vanguard Heating SBVBN(C) Troubleshooting Venting Problems, Flue Gas Spillage, Check Gas Type

Page 12
TROUBLESHOOTING VENTING PROBLEMS

FLUE GAS SPILLAGECAUSES OF SPILLAGE AND CORRECTIVE ACTIONIncorrect Vent SizingVenting Condition® SBVBN(C) AND SBVBP(C)

CAST IRON STOVE AND BURNER SYSTEM

TROUBLESHOOTING VENTING PROBLEMS

Most venting problems are caused by incor- rect vent sizing, improper installation, or inadequate air supply. A preliminary check for a field problem might include:

Using a draft meter to determine if venting system draft meets manufacturer’s specifications

Checking the vent sizing according to manufacturer’s specifications, appliance input, and venting configuration

Examining the entire venting system for faults such as disconnected joints for damaged vent sections

Making sure vent and air openings are not obstructed

If these procedures do not reveal the source of the problem, troubleshooting may include attention to common venting problems.

FLUE GAS SPILLAGE

Spillage occurs when flue gases cannot exit the vent system and back up into the dwell- ing. A primary symptom of appliances equipped with a Vent Safety Shutoff System (flue spill switch) is unexplained appliance shutoffs. Other symptoms of flue gas spillage at the draft hood include condensation on walls and windows and/or noticeable odors. Spillage may also result in the release of carbon monoxide, a colorless, odorless, highly toxic gas. A simple spillage test can be con- ducted if spillage is suspected. See Checking Gas Connection, pages 14 and 15.

CAUSES OF SPILLAGE AND CORRECTIVE ACTION

Incorrect Vent Sizing

If the vent is too small or too short, spillage may occur. If the vent is too large, excessive dilution air may cool flue gases and reduce draft, causing spillage. The vent cap size should also be checked. Check manufacturer’s instructions, appliance in- put rating, and appropriate sizing tables.

Venting Condition

Loose joints can affect draft and cause spill- age. “Mashed” vent sections and damaged vent caps can restrict flow and cause spill- age. Examine and replace as needed.

Obstructions

Small animals or birds may get into and block the vent or draft hood outlet. Dust, lint, and foreign objects may obstruct air inlets. Re- move obstructions and clean openings.

Lateral Run

Lengthy hoizontal or non-vertical runs cause resistance to flow and may reduce draft enough to cause spillage. The pitch of lat- eral runs can also be a problem; lateral runs should be pitched 1/4" rise per foot of hori- zontal run from the appliance to the vent.

Elbows

Too many elbows cause excessive restric- tion of flow and may result in spillage. Usually, two 90º turns can be tolerated in a properly sized venting system. More than two may cause problems and necessitate changing the system.

Negative Pressure in the

Dwelling

An extremely tight house may not supply adequate combustion and venting air. Use of mechanical exhaust such as a dryer vent or range vent may worsen the problem. An air exchange system must be installed in the dwelling to correct this problem.

Flue Gas Cooling

Venting exposed to extremely cold tem- peratures or venting of single wall construc- tion loses heat needed to maintain draft; massive masonry chimneys absorb needed heat. If the flue gases cool excessively, draft is reduced and spillage may result. Use proper materials, insulate and protect prop- erly, reline when necessary.

Down Drafts

In certain wind conditions and in certain relationships with nearby structures and objects, high pressure conditions may affect draft negatively. Relocate the vent cap, raise its height, or use an approved high wind cap.

CAST IRON STOVE AND B-VENT BURNER SYSTEM INSTALLATION

NOTICE: This burner system is intended for use as supplemen- tal heat. Use this burner system along with your primary heating system. Do not install this stove and burner system as your pri- mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this burner system as your primary heat source.

CHECK GAS TYPE

Use proper gas type for the burner system unit you are installing. If you have conflict- ing gas types, do not install burner system. See dealer where you purchased the stove and burner system for proper burner system according to your gas type.

INSTALLING GAS PIPING TO STOVE LOCATION

Obstructions WARNING: A qualified in- staller or service person must connect burner system to gas supply. Follow all local codes.

Lateral Run CAUTION: For propane/LP units, never connect burner sys- tem directly to the propane/LP supply. This burner system re- quires an external regulator (not supplied). Install the external regu- lator between the burner system and propane/LP supply.

For more information, visit www.desatech.com

12

106828

Image 12
Contents OWNER’S OPERATION AND INSTALLATION MANUAL FOR YOUR SAFETYFOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switchSAFETY INFORMATION SBVBNC AND SBVBPC CAST IRON STOVE AND BURNER SYSTEMWARNINGS DANGER Carbon monoxide poisoning may lead to deathPRODUCT FEATURES OWNER’S MANUALPRODUCT IDENTIFICATION LOCAL CODESPRE-INSTALLATION PREPARATION LOCATION AND SPACE REQUIREMENTSetc. in the air exist, may discolor walls CAST IRON STOVE AND B-VENT BURNER SYSTEM ASSEMBLY STOVE BODY ASSEMBLYContinued INSTALLING B-VENT BURNER SYSTEM INTO STOVE BODY INSTALLING OPTIONAL BLOWER ACCESSORYCAST IRON STOVE AND DIRECT-VENT BURNER SYSTEM ASSEMBLY INSTALLING REAR COVERINSTALLATION INSTALLATION PRECAUTIONSTYPE B-VENT INSTALLATION Listed B-0 or Greater VENTINGVENTING INSTALLATION INSTALLATION OF LISTED B-1 VENTINSTALLING VENT SYSTEM IN A CHASE CHECKING VENT CAPACITYHIGH ALTITUDE INSTALLATION CHIMNEYSRELINING SYSTEMS TROUBLESHOOTING VENTING PROBLEMS CAST IRON STOVE AND B-VENT BURNER SYSTEM INSTALLATIONINSTALLING GAS PIPING TO STOVE LOCATION FLUE GAS SPILLAGEInstallation Items Needed CAUTION Use only new, black iron or steel pipe. InterCONNECTING STOVE/ BURNER SYSTEM TO GAS SUPPLY Pressure Testing Gas Supply Piping SystemPressure Testing Burner System Gas Connections CHECKING GAS CONNECTIONSINSTALLING OPTIONAL WALL MOUNT SWITCH GWMS2 INSTALLING OPTIONAL WALL MOUNTED THERMOSTAT - GWMT1Installing Remote Receiver Installing 9-Volt Battery in Hand- Held Remote Control Unit REMOVING/REPLACING GLASS DOORINSTALLING LOGS, LAVA ROCK, AND GLOWING EMBERS Figure 44 - Installing Log NoFigure 45 - Installing Log No Figure 43 - Installing Log No Figure 46 - Installing Log NoFOR YOUR SAFETY READ BEFORE LIGHTING MANUAL LIGHTING PROCEDUREOPERATING STOVE WITH B-VENT BURNER SYSTEM LIGHTING INSTRUCTIONSOPTIONAL REMOTE Thermostat Control OperationGHRC Series Operation GHRCTA Series OperationOPERATING OPTIONAL BLOWER ACCESSORY PILOT ASSEMBLYINSPECTING BURNERS OPERATING OPTIONAL GWMT1 WALL MOUNTED THERMOSTATCLEANING AND MAINTENANCE WARNING Turn off burner system and let cool before cleaningGLASS DOOR PILOT AND BURNERSTROUBLESHOOTING OBSERVED PROBLEMPOSSIBLE CAUSE REMEDYREMEDY Clean pilot see Cleaning and Mainte WARNING If you smell gas Shut off gas supplyDo not try to light any appliance If you cannot reach your gas supplier, call the fire departmentREPLACEMENT PARTS TECHNICAL SERVICEWIRING DIAGRAM SERVICE HINTSSPECIFICATIONS ACCESSORIESRECEIVER AND HAND-HELD REMOTE CONTROL KIT GHRC WALL MOUNTED ON/OFF SWITCH - GWMS2 Not ShownILLUSTRATED PARTS BREAKDOWN SBVBNC SBVBPC23-3 23-4PARTS LIST PART NUMBERDESCRIPTION PARTS AVAILABLE - NOT SHOWNAMITY SCIVFC* SERIES PSCIVFC* SERIES Indicates Color Suffix DesignationPART WARRANTY INFORMATION LIMITED WARRANTY B-VENT BURNER SYSTEM AND AMITY STOVE CHASSISKEEP THIS WARRANTY INTERNATIONAL