Installation & Operation Manual
6 Hydronic piping (continued)
Figure 6-6 Multiple Boilers - Single Temperature Zoned with Zone Valves - DHW Priority
|
|
| Number of Units |
| |||
Model | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
| Required Pipe Sizes |
| ||||
55 | 2" | 2" | 2" | 2" | |||
85 | 2" | 2" | 2" | ||||
110 | 2" | 2" | 3" | ||||
155 | 2" | 2" | 3" | 3" | 4" | ||
199 | 2" | 2" | 3" | 4" | 4" | 4" | |
285 | 3" | 4" | 4" | 4" | 5" | ||
399 | 3" | 4" | 4" | 5" | 5" | 5" |
|
| ZONE #1 |
| PRESSURE |
|
BACKFLOW | REDUCING | ZONE #2 ZONE #3 ZONE #4 |
PREVENTER | VALVE | PRESSURE |
BALL VALVE |
| GAUGE |
| ZONE VALVES | |
(TYPICAL) |
| (TYPICAL) |
| MAKE UP WATER |
|
| SYSTEM SUPPLY | DIFFERENTIAL PRESSURE |
| BYPASS VALVE | |
| SENSOR | (RECOMMENDED) |
AIR SEPARATOR |
| |
|
| SYSTEM |
EXPANSION | CIRCULATOR | |
| TANK |
|
DRAIN POINT |
(TYPICAL) |
BOILER
CIRCULATOR
PRESSURE
RELIEF VALVE
MAY SUBSTITUTE LOW LOSS HEADER
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART
| ||
MIXING VALVE |
| |
(RECOMMENDED) |
| HOT |
(TYPICAL) | DOMESTIC | |
| WATER | |
| HOT WATER | OUT |
| CIRCULATOR |
|
COLD
WATER
IN
BOILER 2 |
(MEMBER 1) |
BOILER 1 (LEADER)
INDIRECT
DHW TANK
TEMPERATURE / |
|
|
| DRAIN |
|
|
| ||
|
|
| UNION | |
PRESSURE |
|
|
| |
GAUGE |
|
|
| (TYPICAL) |
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
41