OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the Output Terminal Lugs or the convenience receptacles (Figure 10). Make sure to read the operation manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a
Over Current Relay
An over current relay (Figure 11) is connected to the main circuit breaker. In the event of an overload, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.
Figure 10. Connecting Loads
Figure 11. Over Current Relay
NOTICE
Remember the overcurrent relay monitors the current flowing from the U,V, and W Output Terminal Lugs to the load.
In the event of a short circuit or over current condition, it will automatically trip the 600 amp main breaker.
To restore power to the Output Terminal Panel, press the reset button on the overcurrent relay and place the main circuit breaker in the closed position (ON).
page 22 — dca220sscu/4i 60 hz generator • operation and Parts manual — rev. #0 (10/25/12)