Multiquip DCA220SSCU4i manual Battery Cable Installation, Alternator, Wiring

Page 31

inspection/SETUP

Battery

This unit is of negative ground DO NOT connect in reverse. Always maintain battery fluid level between the specified marks. Battery life will be shortened, if the fluid level are not properly maintained. Add only distilled water when replenishment is necessary.

DO NOT over fill. Check to see whether the battery cables are loose. Poor contact may result in poor starting or malfunctions. Always keep the terminals firmly tightened. Coating the terminals with an approved battery terminal treatment compound. Replace battery with only recommended type battery. The battery type used in this generator is BCI Group 27.

The battery is sufficiently charged if the specific gravity of the battery fluid is 1.28 (at 68° F). If the specific gravity should fall to 1.245 or lower, it indicates that the battery is dead and needs to be recharged or replaced.

Before charging the battery with an external electric source, be sure to disconnect the battery cables.

Battery Cable Installation

ALWAYS be sure the battery cables (Figure 34) are properly connected to the battery terminals as shown below. The red cable is connected to the positive terminal of the battery, and the black cable is connected to the negative terminal of the battery.

CAUTION

ALWAYS disconnect the negative terminal FIRST and reconnect negative terminal LAST.

Figure 34. Battery Connections

When connecting battery do the following:

1.NEVER connect the battery cables to the battery terminals when the Auto-Off/Reset-Manual Switch is in either the AUTO or MANUAL position. ALWAYS make sure that this switch is in the OFF/RESET position when connecting the battery.

2.Place a small amount of battery terminal treatment compound around both battery terminals. This will ensure a good connection and will help prevent corrosion around the battery terminals.

NOTICE

If the battery cable is connected incorrectly, electrical damage to the generator will occur. Pay close attention to the polarity of the battery when connecting the battery.

CAUTION

Inadequate battery connections may cause poor starting of the generator, and create other malfunctions.

Alternator

The polarity of the alternator is negative grounding type. When an inverted circuit connection takes place, the circuit will be in short circuit instantaneously resulting the alternator failure.

DO NOT put water directly on the alternator. Entry of water into the alternator can cause corrosion and damage the alternator.

Wiring

Inspect the entire generator for bad or worn electrical wiring or connections. If any wiring or connections are exposed (insulation missing) replace wiring immediately.

Piping and Hose Connection

Inspect all piping, oil hose, and fuel hose connections for wear and tightness. Tighten all hose clamps and check hoses for leaks.

If any hose (fuel or oil) lines are defective replace them immediately.

DCA220ssCU/4i 60 hz generator• operation manual — rev. #0 (10/25/12) — page 31

Image 31
Contents Model DCA220SSCU Model DCA220SSCU4i Proposition 65 warning Nhtsa Reporting Safety DefectsSpecifications are subject to change without notice Table of ContentsPage SaFeTY messages Safety InformationGeneraTor saFeTY General saFeTYRestricted. If the air fl ow is Engine saFeTYIf operating in speed ranges above the maximum allowable From fuel vapors or if fuel is spilled on a hot engine Fuel saFeTYToWing saFeTY „ never use fuel as a cleaning agentGrounding safety ElecTrical saFeTYPower cord/cable safety EnvironmenTal saFeTY BaTTerY saFeTYIncludes engine and radiator hoses Includes filters Specifications220 DimensionsTypical Generator Grounding Application InstallationGenerator Grounding Outdoor InstallationIndoor Installation MountingGeneral Information Item no Major ComponentsOption Button This button is not active. Do not use Engine control unit ecuFuel Gauge Indicates amount of diesel fuel available ENGINE/Generator Control PanelTerminal legs O and Ground are considered bonded grounds Output Terminal FamiliarizationOutput Terminal Panel is provided with the following 139V Twist-Lock Auxiliary Receptacles VAC Gfci ReceptaclesOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Voltage Change-Over Board Generator Output VoltagesMaximum Amps AC Ammeter Gauge Reading How to Read the ac ammeter and ac voltage gaugesGenerator OUTPUTS/gauge reading AC Voltmeter Gauge Reading1Ø-120V Uvwo Terminal Output Voltages 1Ø-240V Uvwo Terminal Output Voltages1Ø-480V Uvwo Terminal Output Voltages 3Ø-480V Uvwo Terminal Output Voltages1Ø-277V Uvwo Terminal Output Voltages Fuel Check Inspection/SETUPCircuit Breakers Lubrication OilOnly Fill on Level Ground Refueling ProcedureOperation in Freezing Weather Cleaning the RadiatorAir Cleaner Fan Belt Tension Coolant Antifreeze/Summer Coolant/ WaterAlternator BatteryBattery Cable Installation WiringEngine’s exhaust contains harmful emissions Place the engine speed switch in the LOW down positionBefore Starting Starting ManualVoltmeter Starting Auto Mode Generator START-UP Procedure Auto ModeRemove all loads from the generator Normal Shutdown ProcedureEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyGeneral Inspection Air Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Cleaning Inside the Fuel TankFuel Addition Removing Water from the Fuel TankFlushing Out Radiator and Replacing Coolant Radiator CleaningCheck Oil Level Replacing Oil FilterBattery Charger and Jacket Water Heater Power Connections Diesel Particulate Filter DPF DPF pre-alarmEmission control Diesel Oxidation Catalyst DOCECU DPF Engine Shutdown Forced regeneration procedureTrailer Maintenance Trailer MaintenanceActuator Brake AdjustmentBrakes Hydraulic Surge BrakesTire Wear/Inflation Tires/Wheels/Lug NutsSuspension Never use an pneumatic air gun to tighten wheel lug nuts Lug Nut Torque RequirementsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramTroubleshooting Generator Troubleshooting Diagnostics Page Explanation of Code in Remarks Column Suggested Spare Parts Generator Assy 4A# 0032005000 06018423340601823282 0018205020Generator Assy C1132300114 C1154400103011106015 18-1 031112230Control panel Assy M4223000604 M4223000503M9220100004 Y0080200007Control BOX Assy M4213500104 M4213000212011008020 M4213400104Control BOX Assy 8181852104 0027105016M4273000003 011208030Engine and Radiator Assy Y0602046649 M4923200054Y0602015246 Y0602046648Engine and Radiator Assy 0193600400 Y0603307520Y0605511394 Y0605512192Output terminal Assy 3461860504 C1231700003M9220100304 0801830804Battery Assy 3A# 0602220199M9103000804 0602220920Muffler Assy 0207308000 Y0602300240M4330400003 M2330400704Fuel tank Assy M9310500104 M43630002020605505070 M4363200004Enclosure Assy M4493104603 M4413000412M1413400004 M4423000512Enclosure ASSY. 28A 952404470 06018500970027208025 M4443600004Enclosure ASSY. 51A M4493407704 M445300160350A M4493407604 M4453001703Rubber seals Assy Seal Rubber Nameplate and decals Assy M9520100603 M4550000603M4550000703 M9520100304Nameplate and decals ASSY. M4560100704 M95102000020600500090 0021106016Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help