GENERATOR OUTPUTS
Generator Output Voltages
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by applying jumpers (6) to the voltage
Voltage Change-Over Board
The voltage
Maximum Amps
Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed.
Table 8. Generator Maximum Amps
Model | DCA220SSCU/ | |
DCA220SSCU4i | ||
| ||
Rated Voltage | Maximum Amps | |
|
| |
Single Phase 120 Volt | 488.9 amps (4 wire) | |
|
| |
Single Phase 240 Volt | 244.4 amps (4 wire) | |
|
| |
Three Phase 240 Volt | 529 amps | |
|
| |
Three Phase 480 Volt | 264 amps | |
|
|
Figure 12. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage
Table 7. Voltages Available
UVWO Output | Voltage | Voltage | ||||
Terminal Lugs | ||||||
|
|
|
|
|
|
|
3Ø | 208V | 220V | 240V | 416V | 440V | 480V |
|
|
|
|
|
|
|
1Ø | 120V | 127V | 139V | 240V | 254V | 277V |
|
|
|
|
|
|
|
Voltage |
|
1Ø
120V
N/A
N/A
240V
N/A
N/A
page 24 — dca220sscu/4i 60 hz generator • operation and Parts manual — rev. #0 (10/25/12)