Before Starting
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
1.Place the Control Power switch (Figure 18) on the digital control panel in the up position (ON).
ON (UP)
Figure 18. Control Power Switch (ON)
2.Place the voltage selector switch (Figure 19) in the desired voltage setting position. The corresponding Voltage Status LED on the control panel will light to indicate the selected voltage (Figure 20).
120/208 3
277/480 3
120/240 1
Figure 19. Voltage Selector Switch
120/208 3Ø Position
LIGHTS IF
SELECTED
Figure 20. Voltage Status LEDs
3.If it is necessary to prime engine before starting (such as after changing fuel filter or running out of fuel), place the fuel valves in the prime position (Figure 21). Place the fuel priming switch (Figure 22) in the up position.
VERIFY CIRCUIT | ON |
| |
|
|
| |
BREAKERS ARE ON |
|
|
|
Electronic Trip Unit |
|
| Test |
Push to Trip | A — 500 | E — 1250 |
|
450 AMP | B — 600 | F — 1500 |
|
C — 800 | G — 2000 |
| |
LONG — INST. | D — 1000 | H — 2500 | Status |
Figure 24. Circuit Breakers (ON)
page 34 — SG1400C3 Studio Generator • operation manual — rev. #0 (10/05/11)