Multiquip DCA-150SSKII Output Terminal Panel Available Voltages, Voltage Selector Switch

Page 34

Table of Contents

DCA-150SSKII — OUTPUTTERMINAL PANEL OVERVIEW

Output Terminal Panel Available Voltages

A wide range of voltages are available to supply load to many different applications. Voltages may be selected by using the voltage selector switch and how you hookup your hard wire connection to the generator. To obtain some of the voltages listed, fine adjustment with the Voltage Regulator on the control panel is necessarry. See the table below (Table 8) for a list of available voltages the generator is able to supply.

TABLE 8. VOLTAGES AVAILABLE

MODEL

DCA150SSKll

 

 

 

 

 

 

 

 

 

 

 

 

 

3 PHASE VOLTAGE

208 VOLT

 

220 VOLT

240 VOLT

416 VOLT

440 VOLT

480 VOLT

(SWITCHABLE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE PHASE

120 VOLT

 

127 VOLT

139 VOLT

240 VOLT

254 VOLT

277 VOLT

(SWITCHABLE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Selector Switch

The voltage selector switch is located above the UVWO Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

CAUTION :

NEVER switch Voltage Selector Switch position while the engine is engaged.

Maximum Amps

The following table show the maximum amps the entire generator can provide. Do not exceed the maximum amps listed. (See Table 9)

Table 9. Maximum Amps

Model:

DCA150SSKll

 

 

Rated

Maximum Amps

Voltage

 

 

 

Single Phase

333.3 amps (4 wire)

120 Volt

 

 

 

Single Phase

166.7 amps (4 wire)

240 Volt

 

 

 

Three Phase

361 amps

240 Volt

 

 

 

Three Phase

180 amps

480 Volt

 

 

 

Receptacle Use

When the UVWO terminals are providing power, the receptacle power available decrease. Do not exceed receptacle power available listed on Table 10.

Voltage Selector Switch Locking Button

The voltage selector switch has a locking button to protect the generator and generator load from being switched while the engine is running. To lock the Voltage Selector Switch, press in the red button located on the Voltage Selector Switch, and use a pad lock to hold it into this position.

Over Current Relay

An over current relay is connected to the circuit breaker. In an over current situation, both the circuit breaker and the over current relay may trip. If the circuit breaker can not be reset, the reset button on the over current relay must be pressed. The over current relay is located in the control box.

Table 10. Receptacle Use

 

 

Receptacle

Power in Use

Power

 

 

Available

 

 

 

 

240/120V

Duplex

240/480V

Single Phase

NEMA

3-Phase

or Twist

5-20R 120V

 

Lock CS6369

 

 

 

 

 

KVA

KW

KW

 

 

 

150

87

0

 

 

 

146

85.8

1.2

 

 

 

142

84.6

2.4

 

 

 

138

83.4

3.6

 

 

 

133

82.2

4.8

 

 

 

PAGE 34 —DCA-150SSKII— PARTS AND OPERATION MANUAL — REV. #2 (05/08/01)

Image 34
Contents MQ Power Model DCA-150SSKII Portable Generator Table of Contents Heres HOW to GET Help Table of Contents Parts Ordering Procedures USAGeneral Safety Rules for Safe OperationRules for Safe Operation RadiatorBattery Loading and Unloading CraneTransporting Maintenance SafetyEmergencies Towing Safety Precautions DCA-150SSKII TowingDCA-150SSKII -TRAILER-SAFETY Guidelines Explanation of ChartDCA-150SSKII -TRAILER-SPECIFICATIONS TRLR-10XFDCA-150SSKII -TRAILER-SPECIFICATIONS ElectricalBrakes Electric Brake AdjustmentDCA-150SSKII -TRAILER Braking System Electric BrakesDCA-150SSKII -TRAILER Braking System Hydraulic/Air/Surge BrakesTire Wear/Inflation DCA-150SSKII -TRAILER Tires & SuspensionTires/Wheels/Lug Nuts SuspensionDCA-150SSKII -TRAILERTIRES & Suspension Lug Nut Torque RequirementsDCA-150SSKII Trailer Wiring Diagrams DCA-150SSKII TRAILER-BRAKETROUBLESHOOTING Electric Brake TroubleshootingDCA-150SSKII -TRAILER-BRAKETROUBLESHOOTING Hydraulic Brake TroubleshootingDCA-150SSKII Operation and Safety Decals Machine Safety DecalsDCA-150SSKII Operation and Safety Decals DCA-150SSKII Specifications Generator SpecificationsDCA-150SSKII General Information Page DCA-150SSKII Major Components Major ComponentsDCA-150SSKII Dimensions TOP, SIDE, and Rear DimensionsDCA-150SSKII Control Panel Control PanelDCA-150SSKII Control Panel Mpec ModuleDCA-150SSKII Engine Operating Panel Engine Operating PanelDCA150SSKII Engine Operating Panel Volt Recetacle Connecting LoadDCA-150SSKII Outputterminal Panel Overview Circuit BreakersDCA-150SSKII Outputterminal Panel Overview Output Terminal Panel Available Voltages Voltage Selector SwitchVoltage Selector Switch Locking Button Maximum AmpsHow to read the output terminal guages Output on the selected leg240/120V Hard Wire Hookup 480/240V Hard Wire HookupPhase, 480V, 440V, or 416 Volt Single Phase 480V, 440V, or 416 VoltSingle Phase 277V, 254V, or Phase, 240V, 220V, or 208 Volt Single Phase 240V, 220V, or 208 VoltSingle Phase 139V, 127V, or Single Phase 120 Volt Voltage Selector Switch- Single Phase 240/120V PositionSingle Phase, 240 Volt Outdoor Installation DCA-150SSKII InstallationIndoor Installation DCA-150SSKII Installation Typical Generator Grounding ApplicationGeneral Inspection Prior to Operation DCA-150SSKII PRE-SETUPExtension Cable DCA-150SSKII PRE-SETUP Air Cleaner Fan Belt Tension Cleaning the RadiatorOperation in Freezing Weather Wiring Battery Cable InstallationPiping and Hose Connection Three Phase Load Single Phase LoadDCA-150SSKII Load Application Before Starting Before Starting Generator and Control PanelClose all engine enclosure doors Figure Voltage Meter Volts DCA-150SSKII Generator START-UP Procedure Auto DCA-150SSKII Generator SHUT-DOWN Procedure Engine ShutdownDCA-150SSKII Maintenance DCA-150SSKII Maintenance Inspection / MaintenanceDCA-150SSKII -TROUBLESHOOTING Engine Engine TroubleshootingDCA-150SSKII -TROUBLESHOOTING Engine Engine TroubleshootingDCA-150SSKII -TROUBLESHOOTING GENERATOR/ENGINE Engine & Generator TroubleshootingDCA-150SSKII -TROUBLESHOOTING Mpec Mpec TroubleshootingExplanation of Code in Remarks Column Items Found In the Items Number ColumnQty Description DCA-150SSKII- Generator Assy Generator AssyDCA-150SSKII- Generator Assy DCA-150SSKII Control BOX Assy Control BOX AssyDCA-150SSKII Control BOX Assy DCA-150SSKII- Control BOX Assy DCA-150SSKII- Control BOX Assy DCA-150SSKII- Engine & Radiator Assy Engine & Radiator AssyDCA-150SSKII- Engine & Radiator Assy DCA-150SSKII- Engine & Radiator Assy Hose Band DCA-150SSKII- Engine & Radiator AssyEngine & Radiator ASSY. HoseDCA-150SSKII Engine Operating Panel Assy Engine Operating Panel AssyEngine Operating PanelTable of Contents DCA-150SSKII Engine Operating Panel Assy Engine Operating Panel DCA-150SSKII Battery Assy Battery AssyDCA-150SSKII Battery Assy DCA-150SSKII Muffler Assy Muffler AssyExhaust Pipe DCA-150SSKII Muffler AssyMuffler SheetDCA-150SSKII Fueltank Assy Fuel Tank AssyDCA-150SSKII Fueltank Assy DCA-150SSKII Enclosure Assy Enclosure AssyDCA-150SSKII Enclosure Assy Cato Gold DCA-150SSKII Enclosure Assy DCA-150SSKII Rubber Seals Assy Rubber Seals AssyRubber Seals DCA-150SSKII Rubber Seals AssyDCA-150SSKII Name Plate and Decals Name Plate and DecalsDCA-150SSKII Name Plate and Decals DCA-150SSKII Name Plate and Decals Fuel Tank Group Battery GroupMuffler Group Enclosure GroupEffective July 1 Page 800/421-1244 or 310/537-3700 FAX 310

DCA-150SSKII specifications

The Multiquip DCA-150SSKII is a robust and reliable 150kVA diesel generator designed to meet the demands of various applications, particularly in construction, events, and industrial settings. Engineered for high performance and durability, this generator stands out with its advanced features, technologies, and characteristics.

One of the primary features of the DCA-150SSKII is its powerful Yanmar diesel engine. This engine is renowned for its exceptional fuel efficiency and reliability, ensuring that the generator can run for extended periods without the need for frequent refueling. The engine is designed to meet stringent emissions standards, making the DCA-150SSKII an environmentally friendly option for those needing portable power solutions.

The generator is equipped with a state-of-the-art digital control panel that simplifies the operation and monitoring of the unit. The control panel provides real-time data about the generator's performance, including voltage, frequency, and operational hours, allowing users to efficiently manage power distribution. Additionally, the generator features an automatic voltage regulator that ensures stable and consistent power output, crucial for sensitive electronics and equipment.

The DCA-150SSKII is designed with durability in mind. Its sturdy frame and weather-resistant enclosure protect it from the elements, making it suitable for outdoor use in a variety of conditions. Noise reduction technology is integrated into the design, ensuring that the generator operates quietly, which is particularly beneficial for urban settings or nighttime operations.

Safety is paramount in the design of the DCA-150SSKII. It includes essential safety features such as low oil pressure shutdown, high-temperature shutdown, and overload protection. These features help prevent damage to the generator and ensure safe operation in various environments.

Mobility is another characteristic that sets the DCA-150SSKII apart. It is equipped with a robust chassis and lifting hooks, making it easy to transport from one location to another, whether on a job site or for an event.

In summary, the Multiquip DCA-150SSKII combines power, efficiency, and reliability in a compact design. Its advanced technological features, durability, and safety mechanisms make it an excellent choice for anyone in need of a dependable diesel generator. With its powerful performance and user-friendly operation, the DCA-150SSKII is a top contender in the generator market, meeting the diverse power needs of professionals across various industries.