In many installations it may be desirable to install louvers in the inlet and outlet openings. Louvers may be either stationary or movable. In areas of great temperature variation, it is often best to install movable louvers that can be thermostatically adjusted to regulate air flow and room temperature. See Figure 4-3 and Figure 4-4.

If the set is to be installed in an atmosphere highly contaminated with impurities such as dust, chaff, etc., it may be necessary to install a filter in the inlet opening. Furnace-type filters have been very satisfactory. Again, a certain amount of air flow is lost that must be compensated for by increasing the size of the opening.

The following are minimum air inlet and outlet recommendations:

1.If louvers are used, the size of the opening should be increased approximately 50%.

2.If window screening is used, the opening should be increased approximately 80%.

3.If furnace filters are used, the opening should be increased 120%.

4.2 Air-Cooled Generators

Air-cooled generator sets are available with three basic types of air cooling systems that are discussed separately on the following pages. For air-cooled models 4 kW and smaller, size the air inlet and outlet openings at least 1 square foot (0.092 m2). For larger sets determine inlet and outlet size on the basis of 0.25 square feet (0.023 m2) for each 1000 watts of capacity. A 5000-watt set, for example, requires inlets and outlets of 1.25 square feet (0.115 m2) each:

0.25cu. ft. x 5 kW = 1.25 cu. ft. (0.023 m2 x 5 kW = 0.115 m2)

Air requirements are listed in each model’s specification sheet. Remember to increase the size of openings for louvers, screens, filters, etc. as described earler in this section.

Figure 4-3 Stationary Louvers for Air Inlet

Figure 4-4 Movable Louvers For Air Inlet

12 Section 4 Air Requirements

TP-5700 7/93

Image 24
Contents 20-2800 kW ModelsProduct Identification Information California PropositionTable of Contents Table of Contents TP-5700 7/93 Safety Precautions and Instructions BatteryAccidental Starting Engine Backfire/Flash Fire Exhaust SystemFuel System Hazardous Noise Hazardous Voltage/ Electrical ShockIV Safety Precautions and Instructions TP-5700 7/93 Heavy Equipment Hot PartsMoving Parts VI Safety Precautions and Instructions TP-5700 7/93 Service Assistance IntroductionPage General Typical Stationary-Duty Generator Set Installation Load and Transport Lifting the Generator SetGenerator Set with Lifting Bars in Skid Weather Housing Transporting the Generator SetLoad and Transport TP-5700 7/93 Weight LocationLocation Factors Mounting Mounting Surface DetailVibration Isolation Neoprene-Type Integral Vibration IsolatorsLocation TP-5700 7/93 Air Requirements GeneralAir-Cooled Generators Stationary Louvers for Air InletForced Air Standard Forced-Air Cooling SystemAir-VacCooling System Air-Vac Cooling SystemAir Vent Cooling System using an Air-Cooled Generator Set Air VentLiquid-Cooled Models Unit-Mounted Radiator CoolingRemote Radiator Cooling Air Control LouversCity Water Cooling Cooling Tower12 Cooling Tower System Block Heaters Recommended CoolantExhaust System Exhaust System, Side Inlet SilencerFlexible Section Condensation TrapPiping Double-Sleeve Thimbles Double-Sleeved Thimbles and Rain CapExhaust System TP-5700 7/93 Fuel Systems Diesel Fuel SystemsMain Fuel Tank Fuel LinesTransfer Tanks Diesel Fuel System with Overhead Main Tank and Transfer TankAuxiliary Fuel Pumps Gasoline Fuel Systems Natural or LP Gas Fuel Systems Typical LP Gas Vapor-Withdrawal SystemNatural Gas and LP Gas System, Liquid Withdrawal Flexible Connector Gas PipingFuel Regulators LP Gas Fuel Characteristics Vapor Withdrawal SystemsLiquid Withdrawal Systems Dual Systems Natural and LP GasNatural Gas Combination Gas-GasolineElectrical Requirements BatteriesElectrical Connections Load Lead ConnectionsTerminal Connector Torque 124.3 1100 67.8 600Automatic Transfer Switches Audiovisual AlarmControl Connections Remote AnnunciatorRemote Emergency Stop Switch WiringDry Contact Kit Generator Junction BOX Appendix a Abbreviations AnsiLCB Page 1993, 2001, 2003 by Kohler Co. All rights reserved

20--2800 kW specifications

The Kohler 20-2800 kW generator series is renowned for its exceptional performance and reliability, making it a prime choice for various industrial and commercial applications. Designed for continuous and backup power generation, these generators are capable of providing robust energy solutions for facilities that demand high capacity and efficiency.

One of the standout features of the Kohler 20-2800 kW series is its advanced technology integration. Kohler utilizes the latest in digital control systems, ensuring precise monitoring and management of generator functions. The generator's control panel provides real-time data on power output, fuel consumption, and operating conditions, allowing operators to make informed decisions quickly.

In terms of fuel efficiency, the Kohler generators are engineered to minimize operational costs while maximizing performance. The series includes options for both diesel and natural gas, offering flexibility depending on user requirements and availability. The efficient fuel consumption not only supports cost savings but also aligns with environmental standards, reducing emissions during operation.

Durability and reliability are key characteristics of this generator series. Kohler buildings are constructed using high-quality materials and components that withstand harsh environmental conditions. System redundancy features and robust cooling systems ensure that the generators can operate continuously without failure, making them ideal for critical power needs.

The Kohler 20-2800 kW series also includes noise-reducing technology, making them suitable for installations in noise-sensitive environments. With options for acoustic enclosures, these generators comply with local noise regulations while delivering powerful performance.

Safety features are integrated into the generator design, including automatic shutdown systems for over-speed, low oil pressure, and high water temperature, ensuring that the equipment operates safely during emergencies.

The modular design of the Kohler 20-2800 kW allows for easy installation and maintenance. Access points for service and diagnostics are strategically placed for convenience, reducing downtime and improving efficiency in upkeep.

Overall, the Kohler 20-2800 kW generator series stands out as a dependable powerhouse, combining advanced technology, fuel efficiency, durability, and safety features to meet the demands of various industries. Whether for data centers, manufacturing facilities, or large commercial buildings, Kohler's commitment to quality and innovation makes these generators an exemplary choice for reliable power generation.