Kohler 20--2800 kW manual City Water Cooling, Cooling Tower

Page 30

The engine water pump can be used to circulate water through the remote radiator providing that the vertical distance from the engine water pump does not exceed the engine manufacturer’s recommendations. The allowable static head may range from 17-50 feet (5.2-15.2 m). Consult the Specification Sheet for the unit. This is important because greater height will result in excessive head pressure on engine components, causing problems such as leaking water pump seals. The piping between the engine and remote radiator must be sized for a maximum of 2 psi (0.141 kg/cm2) pressure drop at the rated flow of the engine water pump. A vent line from the engine to the radiator may be necessary to purge air from the cooling system.

When either horizontal or vertical distances exceed the above limitations, a hot well tank or heat exchanger and auxiliary circulating pump as shown in Figure 4-10 should be used. The circulating pump should always be wired in parallel with the remote radiator fan so that both will operate whenever the generator set operates.

Heated water is forced by the engine pump into the “hot” side and then is drawn off by the auxiliary pump and forced into the radiator. After circulating through the radiator, coolant flows back to the cold side of the well where it is removed by the engine water pump. Head pressures are thus isolated from the engine. Pressure can also be isolated by installing a heat exchanger between the engine and remote radiator.

With the radiator at a remote location, it is easily overlooked each time the generator is serviced. For this reason, low water alarms, or automatic “make-up” controls are often included in these systems. Antifreeze is required if the radiator is subject to freezing temperatures.

Shutoff valves should be located between the engine and cooling system to allow for isolation of both systems. This will eliminate the need to drain the entire system during service.

To determine radiator size and air requirements check the Specification Sheet for your model. The amount of air required to ventilate the generator set room or enclosure determines the size of the air inlet and outlet—a ventilating fan is usually necessary as generator heat loss as well as engine heat loss must be dissipated.

4.9 City Water Cooling

These systems utilizes city water and heat exchangers for cooling and are similar to remote radiator systems in

that they require less cooling air than unit-mounted radiator systems. Refer to Figure 4-11 for a view of some of the elements of a typical installation.

The heat exchanger the effects of city water (lime deposits, corrosion) to one side of a heat exchanger which is relatively easy to clean or replace, while engine coolant circulates in a closed system similar to a radiator system.

It allows better control of engine temperature, permits the use of antifreeze and coolant conditioners, and is suited to the use of an engine block heater as a starting aid.

Water inlet and outlet connections are mounted on the generator set skid and isolated from engine vibration by flexible sections. If the generator set is vibration- mounted to the skid and the skid is bolted directly to the mounting base, no additional flexible sections are needed between connection points on the skid and city water lines. If the generator set skid is mounted to the base with vibration isolators, flexible sections must be used between connection points on the skid and city water lines.

A solenoid valve mounted at the inlet connection point automatically opens upon start-up of the generator set, providing water under pressure from city mains for engine cooling. This valve automatically closes when the unit shuts down. Be sure that the solenoid valve is located upstream of the supply flexible connection. An additional customer-supplied valve may be used ahead of the entire system to manually shut off city water when servicing the generator.

4.10 Cooling Tower

In warm, dry climates, a cooling tower may be a suitable source of generator set cooling water. A typical system is shown in Figure 4-12. This is a variation of the city water cooling with heat exchanger. The engine system usually includes the engine water pump, a heat exchanger, a surge tank, and the water jacket of the engine. The raw water system consists of the cooling tower, a raw water pump, and the tube portion of the heat exchanger. Raw water is circulated through the heat exchanger tubes to absorb heat from the engine system which is circulated around the surrounding shell of the heat exchanger. The heated raw water is directed into a pipe at the top of the cooling tower and sprayed down into the tower to cool by evaporation. Since some water is constantly being lost by evaporation, the system must include provision for “make up” water.

18 Section 4 Air Requirements

TP-5700 7/93

Image 30
Contents 20-2800 kW ModelsProduct Identification Information California PropositionTable of Contents Table of Contents TP-5700 7/93 Safety Precautions and Instructions BatteryAccidental Starting Engine Backfire/Flash Fire Exhaust SystemFuel System Hazardous Noise Hazardous Voltage/ Electrical ShockIV Safety Precautions and Instructions TP-5700 7/93 Heavy Equipment Hot PartsMoving Parts VI Safety Precautions and Instructions TP-5700 7/93 Service Assistance IntroductionPage General Typical Stationary-Duty Generator Set Installation Load and Transport Lifting the Generator SetGenerator Set with Lifting Bars in Skid Weather Housing Transporting the Generator SetLoad and Transport TP-5700 7/93 Weight LocationLocation Factors Mounting Mounting Surface DetailVibration Isolation Neoprene-Type Integral Vibration IsolatorsLocation TP-5700 7/93 Air Requirements GeneralAir-Cooled Generators Stationary Louvers for Air InletForced Air Standard Forced-Air Cooling SystemAir-VacCooling System Air-Vac Cooling SystemAir Vent Cooling System using an Air-Cooled Generator Set Air VentLiquid-Cooled Models Unit-Mounted Radiator CoolingRemote Radiator Cooling Air Control LouversCity Water Cooling Cooling Tower12 Cooling Tower System Block Heaters Recommended CoolantExhaust System Exhaust System, Side Inlet SilencerFlexible Section Condensation TrapPiping Double-Sleeve Thimbles Double-Sleeved Thimbles and Rain CapExhaust System TP-5700 7/93 Fuel Systems Diesel Fuel SystemsMain Fuel Tank Fuel LinesTransfer Tanks Diesel Fuel System with Overhead Main Tank and Transfer TankAuxiliary Fuel Pumps Gasoline Fuel Systems Natural or LP Gas Fuel Systems Typical LP Gas Vapor-Withdrawal SystemNatural Gas and LP Gas System, Liquid Withdrawal Flexible Connector Gas PipingFuel Regulators Liquid Withdrawal Systems LP Gas Fuel CharacteristicsVapor Withdrawal Systems Dual Systems Natural and LP GasNatural Gas Combination Gas-GasolineElectrical Requirements BatteriesElectrical Connections Load Lead ConnectionsTerminal Connector Torque 124.3 1100 67.8 600Control Connections Automatic Transfer SwitchesAudiovisual Alarm Remote AnnunciatorRemote Emergency Stop Switch WiringDry Contact Kit Generator Junction BOX Appendix a Abbreviations AnsiLCB Page 1993, 2001, 2003 by Kohler Co. All rights reserved

20--2800 kW specifications

The Kohler 20-2800 kW generator series is renowned for its exceptional performance and reliability, making it a prime choice for various industrial and commercial applications. Designed for continuous and backup power generation, these generators are capable of providing robust energy solutions for facilities that demand high capacity and efficiency.

One of the standout features of the Kohler 20-2800 kW series is its advanced technology integration. Kohler utilizes the latest in digital control systems, ensuring precise monitoring and management of generator functions. The generator's control panel provides real-time data on power output, fuel consumption, and operating conditions, allowing operators to make informed decisions quickly.

In terms of fuel efficiency, the Kohler generators are engineered to minimize operational costs while maximizing performance. The series includes options for both diesel and natural gas, offering flexibility depending on user requirements and availability. The efficient fuel consumption not only supports cost savings but also aligns with environmental standards, reducing emissions during operation.

Durability and reliability are key characteristics of this generator series. Kohler buildings are constructed using high-quality materials and components that withstand harsh environmental conditions. System redundancy features and robust cooling systems ensure that the generators can operate continuously without failure, making them ideal for critical power needs.

The Kohler 20-2800 kW series also includes noise-reducing technology, making them suitable for installations in noise-sensitive environments. With options for acoustic enclosures, these generators comply with local noise regulations while delivering powerful performance.

Safety features are integrated into the generator design, including automatic shutdown systems for over-speed, low oil pressure, and high water temperature, ensuring that the equipment operates safely during emergencies.

The modular design of the Kohler 20-2800 kW allows for easy installation and maintenance. Access points for service and diagnostics are strategically placed for convenience, reducing downtime and improving efficiency in upkeep.

Overall, the Kohler 20-2800 kW generator series stands out as a dependable powerhouse, combining advanced technology, fuel efficiency, durability, and safety features to meet the demands of various industries. Whether for data centers, manufacturing facilities, or large commercial buildings, Kohler's commitment to quality and innovation makes these generators an exemplary choice for reliable power generation.