5.1 Flexible Section

A section of flexible exhaust line should be installed within 2 feet (51 mm) of the engine exhaust outlet. This limits the stress on the engine exhaust manifold or turbocharger resulting from engine motion on its vibration mounts and temperature-induced changes in pipe dimensions. Never allow the engine manifold or turbocharger to support the silencer or exhaust piping weight. The flexible section should be at least 12 inches (305 mm) long.

Where threaded flexible exhaust connectors are used, a 6-8 inch (152-203 mm) length of pipe should separate them from the exhaust manifold. This will serve to reduce the temperature of the flexible connection and extend its life. It also makes it easier to remove the flexible section, if necessary, without putting excessive strain on the engine manifold.

The flexible section should not be bent or used to make up for misalignment between the engine exhaust and the exhaust piping. Since typical exhaust temperatures range from 800°F (427°C) to over 1200°F (649°C) for some engines, seamless stainless steel should be used for the flexible section.

5.2 Condensation Trap

A Y- or tee-type condensation trap with a drain plug or petcock should be installed between the engine and exhaust silencer as shown in Figure 5-3. This will prevent condensed moisture in the engine exhaust from draining into the engine when it is shut down. The trap should be drained of collected moisture periodically.

1

5.3 Piping

Exhaust piping should conform to all applicable codes. In general, exhaust temperatures will be less than 1000°F (538°C) measured at the engine exhaust outlet, except for infrequent brief periods, and standards for low heat appliances will apply. For units with exhaust temperatures below 1000°F (538°C), exhaust piping should be routed a minimum of 18 inches (457 mm) from any combustible materials. If exhaust temperatures will exceed 1000°F (538°C), the minimum distance should be 36 inches (914 mm).

The heat rejected by exhaust piping, and consequently the amount of ventilating air required, can be substantially reduced by insulating exhaust piping with suitable high-temperature insulation. Exhaust temperatures are given on each generator model’s specification sheet.

Placement of exhaust silencer and piping should consider location of combustible materials. If location of exhaust cannot avoid these concerns, use a regular maintenance routine to remove combustible materials. Combustible materials include building materials as well as natural surroundings. Keep dry field grass, foliage, and combustible landscaping material whether or not seasonal a safe distance from the exhaust system.

1. Condensation trap

TP-5700-5

Figure 5-3 Condensation Trap

22 Section 5 Exhaust System

TP-5700 7/93

Image 34
Contents 20-2800 kW ModelsProduct Identification Information California PropositionTable of Contents Table of Contents TP-5700 7/93 Battery Safety Precautions and InstructionsAccidental Starting Exhaust System Engine Backfire/Flash FireFuel System Hazardous Noise Hazardous Voltage/ Electrical ShockIV Safety Precautions and Instructions TP-5700 7/93 Hot Parts Heavy EquipmentMoving Parts VI Safety Precautions and Instructions TP-5700 7/93 Service Assistance IntroductionPage General Typical Stationary-Duty Generator Set Installation Load and Transport Lifting the Generator SetGenerator Set with Lifting Bars in Skid Weather Housing Transporting the Generator SetLoad and Transport TP-5700 7/93 Location WeightLocation Factors Mounting Mounting Surface DetailVibration Isolation Neoprene-Type Integral Vibration IsolatorsLocation TP-5700 7/93 Air Requirements GeneralAir-Cooled Generators Stationary Louvers for Air InletForced Air Standard Forced-Air Cooling SystemAir-VacCooling System Air-Vac Cooling SystemAir Vent Cooling System using an Air-Cooled Generator Set Air VentLiquid-Cooled Models Unit-Mounted Radiator CoolingRemote Radiator Cooling Air Control LouversCity Water Cooling Cooling Tower12 Cooling Tower System Block Heaters Recommended CoolantExhaust System Exhaust System, Side Inlet SilencerCondensation Trap Flexible SectionPiping Double-Sleeve Thimbles Double-Sleeved Thimbles and Rain CapExhaust System TP-5700 7/93 Fuel Systems Diesel Fuel SystemsMain Fuel Tank Fuel LinesTransfer Tanks Diesel Fuel System with Overhead Main Tank and Transfer TankAuxiliary Fuel Pumps Gasoline Fuel Systems Natural or LP Gas Fuel Systems Typical LP Gas Vapor-Withdrawal SystemNatural Gas and LP Gas System, Liquid Withdrawal Gas Piping Flexible ConnectorFuel Regulators Liquid Withdrawal Systems LP Gas Fuel CharacteristicsVapor Withdrawal Systems Dual Systems Natural and LP GasNatural Gas Combination Gas-GasolineElectrical Requirements BatteriesElectrical Connections Load Lead ConnectionsTerminal Connector Torque 124.3 1100 67.8 600Control Connections Automatic Transfer SwitchesAudiovisual Alarm Remote AnnunciatorWiring Remote Emergency Stop SwitchDry Contact Kit Generator Junction BOX Appendix a Abbreviations AnsiLCB Page 1993, 2001, 2003 by Kohler Co. All rights reserved

20--2800 kW specifications

The Kohler 20-2800 kW generator series is renowned for its exceptional performance and reliability, making it a prime choice for various industrial and commercial applications. Designed for continuous and backup power generation, these generators are capable of providing robust energy solutions for facilities that demand high capacity and efficiency.

One of the standout features of the Kohler 20-2800 kW series is its advanced technology integration. Kohler utilizes the latest in digital control systems, ensuring precise monitoring and management of generator functions. The generator's control panel provides real-time data on power output, fuel consumption, and operating conditions, allowing operators to make informed decisions quickly.

In terms of fuel efficiency, the Kohler generators are engineered to minimize operational costs while maximizing performance. The series includes options for both diesel and natural gas, offering flexibility depending on user requirements and availability. The efficient fuel consumption not only supports cost savings but also aligns with environmental standards, reducing emissions during operation.

Durability and reliability are key characteristics of this generator series. Kohler buildings are constructed using high-quality materials and components that withstand harsh environmental conditions. System redundancy features and robust cooling systems ensure that the generators can operate continuously without failure, making them ideal for critical power needs.

The Kohler 20-2800 kW series also includes noise-reducing technology, making them suitable for installations in noise-sensitive environments. With options for acoustic enclosures, these generators comply with local noise regulations while delivering powerful performance.

Safety features are integrated into the generator design, including automatic shutdown systems for over-speed, low oil pressure, and high water temperature, ensuring that the equipment operates safely during emergencies.

The modular design of the Kohler 20-2800 kW allows for easy installation and maintenance. Access points for service and diagnostics are strategically placed for convenience, reducing downtime and improving efficiency in upkeep.

Overall, the Kohler 20-2800 kW generator series stands out as a dependable powerhouse, combining advanced technology, fuel efficiency, durability, and safety features to meet the demands of various industries. Whether for data centers, manufacturing facilities, or large commercial buildings, Kohler's commitment to quality and innovation makes these generators an exemplary choice for reliable power generation.