7.4 Terminal Connector Torque

Use the torque values shown in Figure 7-4 or Figure 7-5 for terminal connectors. Refer to UL-486A, UL-486B, and UL-486E for information on terminal connectors for aluminum and/or copper conductors. See Section 7.2, Electrical Connections, for information on the temperature rating of customer-supplied wire. Comply

with applicable national and local codes when installing a wiring system.

Note: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test the connector using both applicable torque values provided in Figure 7-4.

 

 

 

 

 

 

Tightening Torque, Nm (in. lb.)

 

 

 

 

 

 

 

 

 

 

 

 

Wire Size for Unit

 

 

 

 

 

Hexagonal Head—External

Connection

 

Slot Head 4.7 mm (No. 10) or Larger*

Drive Socket Wrench

 

 

 

 

 

 

 

 

 

 

 

Slot Width <1.2 mm (0.047 in.)

Slot Width >1.2 mm (0.047 in.)

Split-Bolt

Other

AWG, kcmil (mm2)

 

Slot Length <6.4 mm (0.25 in.)

Slot Length >6.4 mm (0.25 in.)

Connectors

Connections

18--10 (0.82--5.3)

2.3 (20)

 

4.0 (35)

9.0

(80)

8.5

(75)

 

 

 

 

 

 

 

 

 

8 (8.4)

2.8 (25)

 

4.5 (40)

9.0

(80)

8.5

(75)

 

 

 

 

 

 

 

 

 

6--4 (13.3--21.2)

4.0 (35)

 

5.1 (45)

18.6

(165)

12.4

(110)

 

 

 

 

 

 

 

 

 

3 (26.7)

4.0 (35)

 

5.6 (50)

31.1

(275)

16.9

(150)

 

 

 

 

 

 

 

 

 

2 (33.6)

4.5 (40)

 

5.6 (50)

31.1

(275)

16.9

(150)

 

 

 

 

 

 

 

 

 

 

1 (42.4)

 

 

 

5.6 (50)

31.1

(275)

16.9

(150)

 

 

 

 

 

 

 

 

 

 

1/0--2/0 (53.5--67.4)

 

 

 

5.6 (50)

43.5

(385)

20.3

(180)

 

 

 

 

 

 

 

 

 

 

3/0--4/0 (85.0--107.2)

 

 

 

5.6 (50)

56.5

(500)

28.2

(250)

 

 

 

 

 

 

 

 

 

 

250--350 (127--177)

 

 

 

5.6 (50)

73.4

(650)

36.7

(325)

 

 

 

 

 

 

 

 

 

 

400 (203)

 

 

 

5.6 (50)

93.2

(825)

36.7

(325)

 

 

 

 

 

 

 

 

 

 

500 (253)

 

 

 

5.6 (50)

93.2

(825)

42.4

(375)

 

 

 

 

 

 

 

 

 

 

600--750 (304--380)

 

 

 

5.6 (50)

113.0

(1000)

42.4

(375)

 

 

 

 

 

 

 

 

 

 

800--1000 (406--508)

 

 

 

5.6 (50)

124.3

(1100)

56.5

(500)

 

 

 

 

 

 

 

 

 

 

1250--2000 (635--1016)

 

 

 

124.3

(1100)

67.8

(600)

 

 

 

 

 

 

 

* For values of slot width or length not corresponding to those specified, select the largest torque value associated with the conductor size.

Slot width is the nominal design value. Slot length is to be measured at the bottom of the slot.

 

 

 

 

 

 

 

Note: If a connector has a clamp screw such as a slotted, hexagonal head screw with more than one means of tightening, test the connector

using both applicable torque values.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7-4 Tightening Torque for Screw-Type Pressure Wire Connectors

 

 

 

 

 

 

 

 

 

 

 

 

 

Socket Size Across Flats,

 

Tightening Torque,

 

 

 

 

 

 

mm (in.)

 

Nm (in. lb.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2

(1/8)

 

5.1

(45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.0

(5/32)

 

11.4

(100)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.8

(3/16)

 

13.8

(120)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.6

(7/32)

 

17.0

(150)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.4

(1/4)

 

22.6

(200)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.9

(5/16)

 

31.1

(275)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.5

(3/8)

 

42.4

(375)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.7

(1/2)

 

56.5

(500)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14.3

(9/16)

 

67.8

(600)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: For values of slot width or length not corresponding to

 

 

 

 

 

 

those specified, select the largest torque value associated

 

 

 

 

 

 

with the conductor size. Slot width is the nominal design

 

 

 

 

 

 

value. Slot length is to be measured at the bottom of the

 

 

 

 

 

 

slot.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7-5 Tightening Torque for Pressure Wire

Connectors with Internal-Drive

Socket-Head Screws

TP-5700 7/93

Section 7 Electrical Requirements 37

Image 49
Contents Models 20-2800 kWCalifornia Proposition Product Identification InformationTable of Contents Table of Contents TP-5700 7/93 Battery Safety Precautions and InstructionsAccidental Starting Exhaust System Engine Backfire/Flash FireFuel System Hazardous Voltage/ Electrical Shock Hazardous NoiseIV Safety Precautions and Instructions TP-5700 7/93 Hot Parts Heavy EquipmentMoving Parts VI Safety Precautions and Instructions TP-5700 7/93 Introduction Service AssistancePage General Typical Stationary-Duty Generator Set Installation Lifting the Generator Set Load and TransportGenerator Set with Lifting Bars in Skid Transporting the Generator Set Weather HousingLoad and Transport TP-5700 7/93 Location WeightLocation Factors Mounting Surface Detail MountingNeoprene-Type Integral Vibration Isolators Vibration IsolationLocation TP-5700 7/93 General Air RequirementsStationary Louvers for Air Inlet Air-Cooled GeneratorsStandard Forced-Air Cooling System Forced AirAir-Vac Cooling System Air-VacCooling SystemAir Vent Air Vent Cooling System using an Air-Cooled Generator SetUnit-Mounted Radiator Cooling Liquid-Cooled ModelsAir Control Louvers Remote Radiator CoolingCooling Tower City Water Cooling12 Cooling Tower System Recommended Coolant Block HeatersExhaust System, Side Inlet Silencer Exhaust SystemCondensation Trap Flexible SectionPiping Double-Sleeved Thimbles and Rain Cap Double-Sleeve ThimblesExhaust System TP-5700 7/93 Diesel Fuel Systems Fuel SystemsFuel Lines Main Fuel TankDiesel Fuel System with Overhead Main Tank and Transfer Tank Transfer TanksAuxiliary Fuel Pumps Gasoline Fuel Systems Typical LP Gas Vapor-Withdrawal System Natural or LP Gas Fuel SystemsNatural Gas and LP Gas System, Liquid Withdrawal Gas Piping Flexible ConnectorFuel Regulators Vapor Withdrawal Systems LP Gas Fuel CharacteristicsLiquid Withdrawal Systems Dual Systems Natural and LP GasCombination Gas-Gasoline Natural GasBatteries Electrical RequirementsLoad Lead Connections Electrical Connections124.3 1100 67.8 600 Terminal Connector TorqueAudiovisual Alarm Automatic Transfer SwitchesControl Connections Remote AnnunciatorWiring Remote Emergency Stop SwitchDry Contact Kit Generator Junction BOX Ansi Appendix a AbbreviationsLCB Page 1993, 2001, 2003 by Kohler Co. All rights reserved

20--2800 kW specifications

The Kohler 20-2800 kW generator series is renowned for its exceptional performance and reliability, making it a prime choice for various industrial and commercial applications. Designed for continuous and backup power generation, these generators are capable of providing robust energy solutions for facilities that demand high capacity and efficiency.

One of the standout features of the Kohler 20-2800 kW series is its advanced technology integration. Kohler utilizes the latest in digital control systems, ensuring precise monitoring and management of generator functions. The generator's control panel provides real-time data on power output, fuel consumption, and operating conditions, allowing operators to make informed decisions quickly.

In terms of fuel efficiency, the Kohler generators are engineered to minimize operational costs while maximizing performance. The series includes options for both diesel and natural gas, offering flexibility depending on user requirements and availability. The efficient fuel consumption not only supports cost savings but also aligns with environmental standards, reducing emissions during operation.

Durability and reliability are key characteristics of this generator series. Kohler buildings are constructed using high-quality materials and components that withstand harsh environmental conditions. System redundancy features and robust cooling systems ensure that the generators can operate continuously without failure, making them ideal for critical power needs.

The Kohler 20-2800 kW series also includes noise-reducing technology, making them suitable for installations in noise-sensitive environments. With options for acoustic enclosures, these generators comply with local noise regulations while delivering powerful performance.

Safety features are integrated into the generator design, including automatic shutdown systems for over-speed, low oil pressure, and high water temperature, ensuring that the equipment operates safely during emergencies.

The modular design of the Kohler 20-2800 kW allows for easy installation and maintenance. Access points for service and diagnostics are strategically placed for convenience, reducing downtime and improving efficiency in upkeep.

Overall, the Kohler 20-2800 kW generator series stands out as a dependable powerhouse, combining advanced technology, fuel efficiency, durability, and safety features to meet the demands of various industries. Whether for data centers, manufacturing facilities, or large commercial buildings, Kohler's commitment to quality and innovation makes these generators an exemplary choice for reliable power generation.