Generac Power Systems 004988-2 Emergency Circuit Isolation Method, Total Circuit Isolation Method

Page 12

Section 2 — Installation

Guardian Liquid-cooled 27 kW and 30 kW Generators

2.5EMERGENCY CIRCUIT ISOLATION

METHOD

This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only crit- ical loads, within the wattage/amperage capacity, dur- ing utility power outages, consider using the emer- gency circuit isolation method.

Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” Load circuits powered by that panel are with- in the wattage/amperage capacity of the generator set. When this method is used, it is difficult to overload the generator. The transfer switch must meet the fol- lowing requirements:

It must have an ampere rating equal to the total amperage rating of the emergency distribution panel circuit.

Have it installed between the building’s main dis- tribution panel and the emergency distribution panel.

2.6TOTAL CIRCUIT ISOLATION

METHOD

When a generator capable of powering all electrical loads in the circuit is to be installed, use the “Total Circuit Isolation Method.” It is possible for the gener- ator to be overloaded when this isolation method is employed. The following apply to the transfer switch in this type of system.

Ampere rating of the transfer switch must equal the ampere rating of the normal incoming utility service.

The transfer switch is installed between the utility service entrance and the building distribution panel.

2.7GROUNDING THE GENERATOR

The National Electrical Code requires the frame and external electrically conductive parts of this equip- ment to be properly connected to an approved earth ground and/or grounding rods. For that purpose, a GROUND LUG (Figure 2.2) is provided on the gener- ator mounting base. Consult a qualified electrician for grounding requirements in the area. Grounding procedures must meet local regulations.

Figure 2.2 – Generator Grounding Lug (typical)

GROUNDING

LUG

DANGER

Do not connect the ground wire to any pipe that carries a flammable or explosive substance

– FIRE or an EXPLOSION may result.

Proper grounding helps protect personnel against electrical shock in the event of a ground fault condi- tion in the generator or in connected electrical devices. In addition, grounding helps dissipate static electricity that often builds up in ungrounded devices.

2.8GENERATOR AC NEUTRAL

CONNECTIONS

Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance. If the neutral wire is grounded and one of the phase loads becomes grounded, the excessive current opens the load circuit breaker or collapses the generator field. The actual result depends on the electrical characteristics of the particular installed generator.

Failure to connect the generator neutral prop-

!erly will result in unbalanced line-to-neutral voltages. Resulting high voltages will cause equipment damage.

2.9TRANSFER SWITCH SIGNAL CONNECTIONS

‹2.9.1 PRE-PACKAGED ATS

If the generator is to be installed with a pre-packaged transfer switch, it is necessary to connect the control wires to the generator and set position two of the four-position dip switch to OFF.

Setting switch two to OFF allows the control PCB to perform the ATS control functions.

10 Generac® Power Systems, Inc.

Image 12
Contents Liquid-cooled, Prepackaged Standby Generators Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents General Hazards Electrical Hazards Transfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Engine Protective DevicesUnpacking Lifting the GeneratorSpecifications Reconfiguring the Fuel System‹ 1.10.1 Generator Specifications ‹ 1.10.2 Engine SpecificationsTorque Specifications Before InstallationEngine OIL Recommendations Coolant RecommendationsGenerator Mounting Support Basic Standby Electric System‹ 2.1.2 Other Published Standards Transfer Switch Signal Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Grounding the GeneratorBattery Installation Preparation Before START-UP‹ 2.9.2 GTS-TYPE ATS Using a Standard GTS Transfer Switch ‹ 3.2.2 Fault Indicator LED ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.5 SET Exercise Time Switch Control Console ComponentsManual Transfer START-UP Engine Governor Adjustments Retransfer and ShutdownAutomatic Operation Weekly Exercise CycleCooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.10 Changing Engine OIL‹ 4.5.12 Spark Plugs Miscellaneous Maintenance ‹ 4.6.1 Cleaning the Generator‹ 4.6.2 Battery ‹ 4.6.3 Battery Maintenance‹ 4.6.4 Battery Replacement Periodic Replacement PartsScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionGuardian Liquid-cooled 27 kW and 30 kW Generators Installation Diagram Customer Connection PCB J2 BCW LOS WLS HCT Starter Carrier Bolt Boot Battery Cable Battery Post Cover BaclkBattery Post Cover RED + Hold Down Battery32 18 Assy GRD Wire 99HSB Assembly BASE-DOOR Ground WireIntake Duct HSB Duct Discharge RH FrontGenerac Power Systems, Inc Assy 2A 12V UL Battery Control BOX HSBDecal AVR Cover Cover Front Panel HSB61 24 Wire SET 3.0L Ford not Not SHOWN-USED to Hold OIL Drain AssemblyCoil Ignition 3.0L Ford Bracket DC ALT 3.0L FordFrame Tank Coolant Recovery Radiator R-IN,L-OUTVenturi 3.0L Ford HSB Side Support Radiator HSBTo B Weldment Mounting Base Flange Fuel InletAssy Regulator 3.0L NG or LPV Washer Flat 5/16 ZincLocktight Rotor 390 15KW 1P Direct HSB 2.5L Ford Rotor 390 20KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumMUFFLER, 3.0L Ford Gasket Exhaust RingExhaust Blanket 750MM Mufflr Strap 6IN DIAElement AIR Cleaner Cover AIR CleanerTube AIR Intake 3.0L Ford Washer Flat M5Warranty Schedule