Section 4 — Maintenance
Guardian
Do not use any jumper cables or booster bat- ! tery to crank and start the generator engine. If
the battery has completely discharged, remove it from the generator for recharging.
| PERIODIC REPLACEMENT PARTS | |
Part Name |
| Generac’s Part Number |
Oil Filter |
| # 0E7180 |
Radiator Cap |
| # 046627 |
Air Cleaner |
| # 0C8127 |
Spark Plug |
| # 0E7079 |
Be sure the AUTO/OFF/MANUAL switch is set to ! the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the battery cables are connected.
Be sure the UTILITY power supply is turned off, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
4.6.4 BATTERY REPLACEMENT
When replacing batteries, use the same number and the type of battery that follows:
| BCI Group No. | CCA |
|
| 26/26R | 525 @ 0 deg. F |
|
| 27 | 600 @ 0 deg. F |
|
|
|
|
|
NOTE:
The BCI number should be located directly on the battery.
Generac® Power Systems, Inc. 19