Generac Power Systems 004917-2 owner manual Weekly Exercise Cycle

Page 17

Section 4 — Maintenance

QUIETSOURCELiquid-cooled 30 kW Generators

3.6 AUTOMATIC OPERATION

Figure 3.2 - “Set Exercise” Switch

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

3.7WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

1.Place the AUTO/OFF/MANUAL switch in the AUTO position.

2.Press and hold the “Set Exercise” switch for three seconds, then release.

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in manual mode, or automatically start and run if UTILITY is lost while in Auto mode, but it will not perform a weekly exercise cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switch to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

 

 

S

 

 

 

S

 

FUSE

F

U

F

 

F

U

F

 

S

 

 

S

E

 

E

 

 

 

 

FUSE

 

 

U

4A

 

S

E

 

S

E

 

U

 

15A

 

U F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAT.

MAIN

CHARGER

 

 

AUTO

OFF

 

 

OFF

ON

 

SET

MANUAL

EXERCISE

 

TIME

 

4.1MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

A. EVERY THREE MONTHS

1.Check battery state of charge and condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

B. ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

C. ONCE ANNUALLY

1.Test engine governor. Adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

D. FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 oper- ating hours or 6 months, whichever comes first.)

2.Retorque cylinder head. (See Torque Specs, Section 1.13.)

3.Retorque intake and exhaust manifold. (See Torque Specs, Section 1.13.)

E. EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

Generac® Power Systems, Inc. 15

Image 17
Contents Installation ‹ Operation and Maintenance Authorized Service Dealer Location‹ HOW to Obtain Service IntroductionTable of Contents General Hazards Electrical Hazards Generator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemLifting the Generator UnpackingReconfiguring the Fuel System Specifications‹ 1.10.1 Generator Specifications ‹ 1.10.2 Engine SpecificationsBefore Installation Torque SpecificationsEngine OIL Recommendations Coolant RecommendationsGenerator Mounting Support Generator LocationBasic Standby Electric System ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Transfer Switch Signal ConnectionsTotal Circuit Isolation Method Generator AC Neutral Connections‹ 2.10.1 Vented Batteries Battery Installation‹ 2.9.2 GTS-TYPE ATS Preparation Before START-UP Using a Standard GTS Transfer Switch‹ 3.2.2 Fault Indicator LED ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.5 SET Exercise Time Switch Control Console Components‹ 3.2.6 System Ready LED Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Weekly Exercise Cycle Checking Fluid Levels Cooling SystemOverload Protection for Engine DC Electrical System ‹ 4.5.4 Inspect Cooling System ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.5.5 Check Engine Coolant Level ‹ 4.5.6 Perform Visual Inspection‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.6.2 Battery ‹ 4.5.12 Spark Plugs‹ 4.6.4 Battery Replacement ‹ 4.6.3 Battery MaintenanceService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsCustomer Connection PCB J2 ICT LOS WLS HCT Starter Carrier Bolt Battery Post Cover Baclk Boot Battery CableBattery Post Cover RED + Hold Down BatteryDetail ASSEMBLY,BASE-DOOR Ground Wire Assy GRD Wire 99HSBDuct Intake MID AL Duct Discharge RH ALGenerac Power Systems, Inc Control BOX HSB Assy 2A 12V UL BatteryCover Front Panel HSB Cover TOP Panel HSB512 Cover Flywheel Access Shown 0LHSB Wire SET 3.0L Ford notNot SHOWN-USED to Hold OIL Drain Assembly Washer Lock M12Frame Radiator R-IN,L-OUT Tank Coolant RecoveryVenturi 3.0L Ford HSB Side Support Radiator HSBNER Flange Fuel Inlet Weldment Mounting BaseAssy Regulator 3.0L NG or LPV Washer Flat 5/16 ZincLeads Rotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 40KW 1P Direct HSB 3.9L ChryslerExhaust Flange 2 Pipe OUTPipe Muffler OUT Washer Lock 3/8 SSCover AIR Cleaner ELEMENT, AIR CleanerTube AIR Intake 3.0L Ford Washer Flat M5Installation Diagram Quietsource Liquid-cooled 30 kW Generators This Warranty Shall not Apply to the Following

004917-2 specifications

Generac Power Systems 004917-2 is a noteworthy addition to the realm of home power solutions, designed to provide reliable backup power during outages and enhance energy management for residential users. This model is recognized for its robust engineering and advanced features, making it a preferred choice for homeowners seeking uninterrupted power supply.

One of the standout characteristics of the 004917-2 is its quiet operation, achieved through innovative noise-reduction technology. This feature ensures that users can enjoy a peaceful environment without the disruptive sounds often associated with traditional generators. The unit is designed not only for functionality but also for discretion, seamlessly blending into residential settings.

Built with a powerful engine, the 004917-2 delivers an impressive wattage capacity, ensuring that essential appliances such as refrigerators, lights, and heating systems can function smoothly during power outages. Its automatic transfer switch capability is a significant technological advancement, allowing the generator to detect power loss and activate without user intervention. This means that homeowners can have peace of mind knowing that their critical systems will remain operational when most needed.

Another notable feature of the Generac 004917-2 is its user-friendly control panel, equipped with digital indicators that provide real-time monitoring of the generator's performance. This interface allows users to easily assess power usage, fuel levels, and maintenance schedules, empowering them with the information necessary to manage their energy needs effectively.

Moreover, the 004917-2 is designed for fuel efficiency, incorporating eco-friendly technologies that optimize fuel consumption while delivering high power output. This design not only helps to reduce operational costs but also minimizes the environmental impact.

In terms of durability, the unit boasts a corrosion-resistant exterior that enhances its lifespan, making it suitable for various climates and conditions. Generac's commitment to quality assurance is evident in the rigorous testing that each model undergoes before reaching the consumer market.

In summary, the Generac Power Systems 004917-2 stands out as a reliable and efficient solution for homeowners looking for dependable backup power. With its quiet operation, powerful performance, automatic transfer capabilities, user-friendly interface, fuel efficiency, and robust construction, it meets the demands of modern energy use while offering peace of mind during unexpected outages.