Generac Power Systems 004917-2 Miscellaneous Maintenance, ‹ 4.5.12 Spark Plugs, ‹ 4.6.2 Battery

Page 20

Section 4 — Maintenance

QUIETSOURCELiquid-cooled 30 kW Generators

Figure 4.3 – Engine Air Cleaner

See the “Service Schedule,” Section 6, for air cleaner maintenance.

‹4.5.12 SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as necessary. See Section 6.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com- mercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule,” Section 6, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025 inch) by carefully bending the ground electrode (Figure 4.4).

Figure 4.4 – Setting the Spark Plug Gap

SET PLUG GAP AT 0.5-0.6 mm

(0.020-0.025inch)

4.6MISCELLANEOUS MAINTENANCE

‹4.6.1 CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year, have the generator cleaned and inspected by an Authorized Service Dealer. That deal- er will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹4.6.2 BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

‹4.5.13 COOLANT CHANGE

Every year, have Authorized Service Facility drain, flush and refill the cooling system. See SPECIFICA- TIONS (Section 1.10) for cooling system recommen- dations.

18 Generac® Power Systems, Inc.

Image 20
Contents Installation Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents General Hazards Electrical Hazards Transfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemUnpacking Lifting the GeneratorSpecifications Reconfiguring the Fuel System‹ 1.10.1 Generator Specifications ‹ 1.10.2 Engine SpecificationsTorque Specifications Before InstallationEngine OIL Recommendations Coolant RecommendationsGenerator Location Generator Mounting SupportBasic Standby Electric System ‹ 2.1.1 Nfpa StandardsTransfer Switch Signal Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Generator AC Neutral Connections‹ 2.10.1 Vented Batteries Battery Installation‹ 2.9.2 GTS-TYPE ATS Using a Standard GTS Transfer Switch Preparation Before START-UP‹ 3.2.1 AUTO/OFF/MANUAL Switch ‹ 3.2.2 Fault Indicator LED‹ 3.2.5 SET Exercise Time Switch Control Console Components‹ 3.2.6 System Ready LED Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Weekly Exercise Cycle Checking Fluid Levels Cooling SystemOverload Protection for Engine DC Electrical System ‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.4 Inspect Cooling System‹ 4.5.5 Check Engine Coolant Level ‹ 4.5.6 Perform Visual InspectionMiscellaneous Maintenance ‹ 4.6.1 Cleaning the Generator‹ 4.6.2 Battery ‹ 4.5.12 Spark Plugs‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionCustomer Connection PCB J2 ICT LOS WLS HCT Starter Carrier Bolt Boot Battery Cable Battery Post Cover BaclkBattery Post Cover RED + Hold Down BatteryDetail Assy GRD Wire 99HSB ASSEMBLY,BASE-DOOR Ground WireDuct Intake MID AL Duct Discharge RH ALGenerac Power Systems, Inc Assy 2A 12V UL Battery Control BOX HSBCover Front Panel HSB Cover TOP Panel HSB512 Wire SET 3.0L Ford not Cover Flywheel Access Shown 0LHSBNot SHOWN-USED to Hold OIL Drain Assembly Washer Lock M12Frame Tank Coolant Recovery Radiator R-IN,L-OUTVenturi 3.0L Ford HSB Side Support Radiator HSBNER Weldment Mounting Base Flange Fuel InletAssy Regulator 3.0L NG or LPV Washer Flat 5/16 ZincLeads Rotor 390 15KW 1P Direct HSB 2.5L Ford Rotor 390 20KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 40KW 1P Direct HSB 3.9L ChryslerOUT Exhaust Flange 2 PipePipe Muffler OUT Washer Lock 3/8 SSELEMENT, AIR Cleaner Cover AIR CleanerTube AIR Intake 3.0L Ford Washer Flat M5Installation Diagram Quietsource Liquid-cooled 30 kW Generators This Warranty Shall not Apply to the Following

004917-2 specifications

Generac Power Systems 004917-2 is a noteworthy addition to the realm of home power solutions, designed to provide reliable backup power during outages and enhance energy management for residential users. This model is recognized for its robust engineering and advanced features, making it a preferred choice for homeowners seeking uninterrupted power supply.

One of the standout characteristics of the 004917-2 is its quiet operation, achieved through innovative noise-reduction technology. This feature ensures that users can enjoy a peaceful environment without the disruptive sounds often associated with traditional generators. The unit is designed not only for functionality but also for discretion, seamlessly blending into residential settings.

Built with a powerful engine, the 004917-2 delivers an impressive wattage capacity, ensuring that essential appliances such as refrigerators, lights, and heating systems can function smoothly during power outages. Its automatic transfer switch capability is a significant technological advancement, allowing the generator to detect power loss and activate without user intervention. This means that homeowners can have peace of mind knowing that their critical systems will remain operational when most needed.

Another notable feature of the Generac 004917-2 is its user-friendly control panel, equipped with digital indicators that provide real-time monitoring of the generator's performance. This interface allows users to easily assess power usage, fuel levels, and maintenance schedules, empowering them with the information necessary to manage their energy needs effectively.

Moreover, the 004917-2 is designed for fuel efficiency, incorporating eco-friendly technologies that optimize fuel consumption while delivering high power output. This design not only helps to reduce operational costs but also minimizes the environmental impact.

In terms of durability, the unit boasts a corrosion-resistant exterior that enhances its lifespan, making it suitable for various climates and conditions. Generac's commitment to quality assurance is evident in the rigorous testing that each model undergoes before reaching the consumer market.

In summary, the Generac Power Systems 004917-2 stands out as a reliable and efficient solution for homeowners looking for dependable backup power. With its quiet operation, powerful performance, automatic transfer capabilities, user-friendly interface, fuel efficiency, and robust construction, it meets the demands of modern energy use while offering peace of mind during unexpected outages.