Generac Power Systems 43735, 43734, 43733, 46263 Sequence of Automatic Operation, Engine Heater

Page 15

Section 3 — Operation

Guardian Liquid-cooled 40 kW Generator

‹3.2.2 “OFF” POSITION

This switch position shuts down the engine. This posi- tion also prevents operation.

‹3.2.3 “MANUAL” POSITION

Set the switch to Manual to crank and start the engine. Transfer to standby power will not automatically occur unless there is a utility failure.

With the switch set to AUTO, the engine may

!crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a preset level or during the normal exercise cycle. To pre- vent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.

3.3AUTOMATIC TRANSFER OPERATION

To select automatic operation, do the following:

1.Make sure the transfer switch main contacts are set to their “Utility” position, i.e., loads connected to the utility power source.

2.Be sure that normal utility power source voltage is available to transfer switch terminal lugs N1 and N2.

3.Set the generator’s Auto/Off/Manual switch to AUTO.

4.Set the generator’s main circuit breaker to its ON (or closed) position.

With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to “Sequence of Automatic Operation.”

Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.

The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:

A.Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below about 60 per- cent of the nominal supply voltage, the sensor ener- gizes a 15-second timer.

Once the timer has expired, the engine will crank and start.

B.Engine Warm-up Time Delay

This mechanism lets the engine warm up for about 10 seconds before the load is transferred to a stand- by source.

C.Standby Voltage Sensor

This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.

D.Utility Voltage Pickup Sensor

This sensor monitors utility power supply voltage. When that voltage is restored above 80 percent of the nominal source voltage, a retransfer time delay starts timing.

E.Retransfer Time Delay

This timer runs for about 15 seconds.

At end of a 15-second delay, circuit board action de- energizes transfer relay in the transfer switch.

Retransfer to utility power source then occurs.

F.Engine Cool-down Timer

When the load is transferred back to utility power source, the engine cool-down timer starts timing.

The timer will run for about one minute, and the generator will then shut down.

3.4SEQUENCE OF AUTOMATIC

OPERATION

The generator’s control panel houses a control logic cir- cuit board. This board constantly monitors utility power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).

3.5ENGINE HEATER

This Generac standby generator comes equipped with a block heater (Figure 3.2, page 14) that is similar to the block heaters used in automotive applications. The block heater must be connected to a customer supplied 120V AC circuit.

Generac® Power Systems, Inc. 13

Image 15
Contents 0046262, 0046263 Authorized Dealer Location IntroductionIntroduction Inside Front Cover General Hazards Electrical Hazards Generator AC Connection Systems Prepackaged Transfer SwitchUNPACKING/INSPECTION GeneratorSpecifications Main Circuit BreakerEngine Protective Devices Fuel Requirements Recommendations ‹ 1.8.2 Generator and Load Compatibility‹ 1.9.1 Conversion to LP GAS Vapor Emissions Control System Coolant‹ 1.12.1 AIR Fuel Ratio Controller Other Published Standards Standby Generator InstallationBasic Standby Electric System Nfpa StandardsGrounding the Generator Transfer Switch Start Signal Connections‹ 2.6.1 PRE-PACKAGED Type Switch MethodBattery Installation Preparation Before START-UP‹ 2.7.1 Vented Batteries ‹ 2.8.4 Generator SET Lubrication ‹ 2.8.2 Transfer Switch‹ 2.8.1 Prior to Initial START-UP ‹ 2.8.3 Fuel SystemUsing the AUTO/OFF/MANUAL Switch Sequence of Automatic Operation Engine Heater‹ 3.2.3 Manual Position Checking the Engine OIL Level Weekly Exercise Cycle‹ 4.2.1 Engine OIL Recommendations Changing the Engine AIR Cleaner‹ 4.2.2 OIL and Filter Change Procedure Changing the Engine OIL and FilterBattery Maintenance ‹ 4.5.1 Battery ReplacementSpark Plugs DC Fuse Miscellaneous MaintenanceCooling System Overload Protection forOUT of Service Procedure ‹ 4.11.1 Removal from Service‹ 4.11.2 Return to Service SYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data TS1 Generator D4992-A Guardian Liquid- Panel 4.3L Drawing No Section Wiring Diagram Control Panel Model No KW Generators No D6975 EC1 ACT Drain Pan Oil QTY Description Base Frame Assembly M6 Hinge Panel Face Panel BTM & Back Control Exploded Views and Parts Lists Cover Plate AVR ALT Leads Sensing Wire QTY To Engine Flywheel Washer Lock M12 Exploded Views and Parts Lists Engine 4.3L GM Exploded Views and Parts Lists MOUNT, Engine R & L KIT Radiator Copper Brass DIA. Clamp Assembly 2 Compartment To Engine Front NUT Wing 1/4-20 Nylk To Stepper Motor Support Solenoid NAT GAS Attach to REGULATOR, N/G R600S Exploded Views and Parts Lists Muffler Catalyst 4.3L Assembly Motor Stepper To Thermostat Housing Guardian Liquid-cooled 40 kW Generators Guardian Liquid-cooled 40 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule