Section 6 — Electrical Data
Guardian
Mounting Dimensions - Drawing No. 0D5335
NOTE 7
220 [8.65"]
|
| R677 [R26.66"] |
|
| TYP |
|
| ALT |
247 [9.73"] |
| AIR |
|
204 [8.03"]
794 [31.28"]
RECOMMENDED FUEL/ELECTRICAL
DESCRIPTION |
| INSIDE |
| BASE | |
|
| |
AC LOAD LEAD CONDUIT | (LEFT) | A1 |
INSIDE |
| C |
FUEL CONNECTIONS |
| |
|
|
NOTE:
FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS (SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM
839 [33.01 TYP
C
A1
AREA
MODIFICATIONS REQUIRED FOR INSIDE
49 [1.92"]
TYP
MOUNTING HOLES | AIR | ||
OUT | |||
Ø13.5 [Ø0.53"] |
| ||
| NOTE 1 | ||
8 HOLES ON BOTTOM | |||
| |||
110 [4.33"] TYP. |
| ||
570 [22.44"] TYP. |
| ||
|
| TOP OR PLAN VIEW | |
|
| 2397 [94.37"] | |
|
| 454 [17.87"] | |
NOTE 9 | |||
|
1117 [43.98"]
53 [2.09"]
835 [32.87"]
936 [36.85"]
LEFT SIDE VIEW
NOTES:
140 [5.50"]
TYP
71 [2.79"]
37 [1.44"]
665 [26.19"]
NOTE 2
NOTE 6
103 [4.06"]
3/4" NPT FEMALE
OIL DRAIN
1/2" N.P.T. FEMALE
WEIGHT DATA
UNIT: 729.7 kg [1609 lbs]
STEEL COMPARTMENT: 208.6 kg [460 lbs]
UNITS: mm [INCHES]
965 [37.99"]
1160 [45.67"]
877 [34.51"]
REAR VIEW
1.STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION
2.CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND
ENGINE AUTOMATIC START/STOP CONTROL WIRES PROVIDED IN AC CONNECTION PANEL.
3.EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.
4.12 VOLT NEGATIVE GROUND SYSTEM
BATTERY TRAY INSIDE DIMENSIONS: 178 X 342.5 [7" X 13.5"]
5.2.5" I.D. FLEX EXHAUST
6.MAIN LINE CIRCUIT BREAKER.
7.DOORS MUST BE OPENED 90 DEG. TO BE REMOVED.
8. A1 MAY BE USED | FOR CIRCUIT BREAKER |
9.SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.
ENGINE SERVICE CONNECTIONS
INLET NATURAL GAS = 3/4" NPT COUPLING
OIL DRAIN = 1/2" NPT COUPLING
EXHAUST OUTLET - | 2.5" OD MUFFLER OUTLET |
LIFTING EYE (4 PLACES)
(1)12V BATTERY SEE NOTE 4
GRAVITY 981 [38.62"]
1930 [75.98"]
RIGHT SIDE VIEW
Generac® Power Systems, Inc. 21