Generac Power Systems 009600-5, 009734-5 Cooling and Ventilating AIR, Compartment Floor Cutouts

Page 28

Section 6 – Installation

PRIMEPACT 66G and 66LP Recreational Vehicle Generators

6.2.5 COMPARTMENT FLOOR CUTOUTS

You must provide openings in the generator compart- ment for the following items (Figure 6.8, Page 25):

Engine exhaust and cooling air outlets

Generator cooling air inlet

Four holes for passage of generator mounting bolts. See Section 6.1.4 (Page 23).

Fuel lines and exhaust piping must not penetrate into the vehicle living area.

6.3.2 COOLING AIR INLET OPENINGS

The minimum size of the air inlet opening, whether the generator is housed in a conventional compartment or not, is at least 100 square inches (see Figure 6.10). This rule applies whether inlet air is brought in through an opening in the compartment door, an opening in the vehicle skirt, through ductwork, or by any other means.

NOTE:

Screening, louvers or expanded metal that cover air openings restrict airflow. You must compensate for this by making the actual air opening proportionate- ly larger. See Section 6.3.3 (Page 27).

6.3COOLING AND VENTILATING AIR

It is absolutely essential that an adequate flow of air for cooling, ventilating and engine combustion be supplied to the generator set. Without sufficient airflow, the engine/generator quickly overheats. Such overheating can cause serious operating difficulties and also may cause fire and personal injury. The installer must make sure that sufficient air is available to the generator for cooling, ventilating and combustion. The installer also must provide for a path for exhausting the cooling air to the exterior of a compartment, if so equipped.

Never use discharged cooling air for heating or permit such air to enter the vehicle interior. This air contains deadly carbon monoxide gas and other poisonous, flammable or explosive gases.

6.3.1 GENERATOR AIRFLOW

Engine operation drives cooling fans for the two-stage cooling air system. A pressure fan draws cooling air into the top of the generator (Figure 6.9). This airflow cools the engine/generator and electronic components. The second part of the cooling system, a suction fan, draws air that is heated from a hot engine into a collector pan at the base of the unit. This heated air (although cooler than exhaust muffler) is then deflected out the bottom toward the ground.

Figure 6.9 – Airflow Through Engine/Generator

Figure 6.10 – Air Inlet in Compartment Door

NOTE:

Be sure to meet the minimum clearances illustrated in Figure 6.4 (Page 23).

When the unit is installed on a suspended mounting system, one of several different methods of supplying airflow may be used as follows:

Provide a door in the vehicle skirt having an air inlet opening (Figure 6.11).

Figure 6.11 – Suspended Mount: Inlet Door

• Using ductwork (Figure 6.12, Page 27). The installer must be sure air is available to the top of the genera- tor since air inlets are located at the top.

• By providing an opening in the vehicle skirt and space

26 Generac® Power Systems, Inc.

Image 28
Contents Power SYSTEMS, INC Authorized Service Dealer Location IntroductionTable of Contents General Hazards Electrical Hazards Generator Identification Reference Number IdentificationInstallation SafetyGenerator Applicability Generator AC Connection SystemSpecifications Fuel Consumption gph/lbs.phFuel Requirements Engine OIL RequirementsGenerator Control Panel Automatic Choke Optional Remote START/STOP PanelBefore Starting the Engine Stopping the Generator Starting the GeneratorEngine Exhaust GAS Letting the Engine StabilizeHigh Temperature Switch LOW OIL Pressure SwitchProtection Systems Field BoostChecking the Engine OIL Level Overvoltage Protection6 25-HOUR CHECK-UP 5 25-HOUR BREAK-IN PeriodCleaning the Foam Precleaner Maintaining the Engine AIR CleanerChanging the Engine OIL AND/OR OIL Filter Checking the Engine Spark Plug Clean AIR Intake ScreenSpark Arrestor Muffler Cleaning the Generator Battery MaintenanceWeekly Every SIX MonthsOUT of Service Procedure Drive BeltExercising the Generator Wattage Reference GuidePrimepact 66G and 66LP Recreational Vehicle Generators Part General Hazards Electrical Hazards Purpose and Scope Installation Instructions Standards BookletsEquipment Description Generator Engine Operating SpeedMajor Features and Dimensions Location and Support Generator SupportGenerator Location Suspended MountingGenerator Compartments Generator RestraintCompartment Construction Compartment SizeSound Insulating Materials AcousticsCompartment Floor Cutout Cooling and Ventilating AIR Compartment Floor CutoutsCooling AIR Inlet Openings Generator AirflowGasoline Fuel System Testing the InstallationCompensating for Restrictions Generator Fuel Supply Line LP GAS Fuel SystemParts not Included in Fuel System Primary Regulator Some Important ConsiderationsVapor Withdrawal Gaseous CarburetionExhaust System Fuel Supply LinesExcess Flow Valve Leakage TestsExhaust System Safety WiringElectrical Connections Type of Exhaust SystemBattery Installation Battery Cables 18 Transfer Switch Isolation MethodOptional Accessories Battery Cable ConnectionsBattery Compartment Remote Panel ModelsPost Installation Tests Testing Under LoadBefore Initial START-UP Initial StartInstallation Checklist Troubleshooting Guide Problem Cause CorrectionGenerac Power Systems, Inc Electrical Data Exploded Views and Parts Lists QTY Description To Engine BASE, Mounting To Engine BASE, Mounting To Engine Ground Item Part NO. QTY. Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists Carburetor Assemby CARB. V-TWIN L/P Primepact 66G and 66LP Recreational Vehicle Generators Primepact 66G and 66LP Recreational Vehicle Generators Primepact 66G and 66LP Recreational Vehicle Generators MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingGenerac Power SYSTEMS, INC