Section 6 – Installation

PRIMEPACT 66G and 66LP Recreational Vehicle Generators

behind the generator for cooling airflow (Figure 6.13 ). Recommended clearance behind the back of the generator is at least 1/2 inch (13 mm).

Figure 6.12 – Air Inlet Using Ductwork

Figure 6.13 – Air Inlet in Vehicle Skirt

VEHICLE FLOOR

VEHICLE

 

 

SKIRT

 

AIR

 

INLET

MINIMUM

 

CLEARANCE

 

1-1/2"

 

6.3.4 TESTING THE INSTALLATION

Generac recommends testing the installation to be sure adequate cooling airflow is available to the unit before placing the unit into service. If the unit shows signs of overheating, you will need to enlarge the air openings. Never place a unit into service until absolutely certain that cooling and ventilation is adequate.

NOTE:

You must test the installation, especially if you bring in air from below the generator set.

6.4GASOLINE FUEL SYSTEM

The installation of a gasoline fuel system (Figure 6.14) for a recreational vehicle generator set must comply with applicable codes, standards and regulations. The entire fuel system must be completely free of leaks. There must be no possibility of gasoline vapors entering the vehicle interior.

Figure 6.14 – Generator Fuel System

Fuel Pump

Fuel Filter

6.3.3 COMPENSATING FOR RESTRICTIONS

Such materials as screening, louvers or expanded metal can restrict the free flow of air. Compensate for this restriction by making the actual air opening propor- tionately larger.

Some materials may offer only a 60 percent “free air inlet area.” Other more efficient materials may provide up to a 90 percent free air inlet area. The percentage of free air inlet opening is usually available from the mate- rial supplier or manufacturer.

To determine the actual air inlet opening size required, divide 100 square inches by the percent- age of free air inlet area for the material you will use.

For example: If you plan to use screening with an 80 percent free air inlet area, divide 100 by 0.8, which results in 125 square inches. Minimum actual size of air inlet opening in this case is 125 square inches.

Fuel Line

Gasoline is highly flammable, and its vapors are explosive. Comply with all codes, standards and regulations pertaining to gasoline fuel systems used in recreational vehicle generators. Properly install and maintain the fuel system and keep it entirely free of leaks. Gasoline vapors must not enter the vehicle interior.

Factory installed generator fuel system components include (a) fuel filter, (b) 12-volt DC electric pump, (c) engine carburetor, and (d) interconnecting lines and fit- tings. Connect a fuel supply line to the fuel filter inlet. Use a flexible length of approved fuel hose between the fuel filter inlet connection and rigid fuel lines.

Generac® Power Systems, Inc. 27

Image 29
Contents Power SYSTEMS, INC Introduction Authorized Service Dealer LocationTable of Contents General Hazards Electrical Hazards Reference Number Identification Generator IdentificationSafety InstallationGenerator Applicability Generator AC Connection SystemFuel Consumption gph/lbs.ph SpecificationsFuel Requirements Engine OIL RequirementsGenerator Control Panel Before Starting the Engine Optional Remote START/STOP PanelAutomatic Choke Starting the Generator Stopping the GeneratorEngine Exhaust GAS Letting the Engine StabilizeLOW OIL Pressure Switch High Temperature SwitchProtection Systems Field BoostOvervoltage Protection Checking the Engine OIL Level6 25-HOUR CHECK-UP 5 25-HOUR BREAK-IN PeriodChanging the Engine OIL AND/OR OIL Filter Maintaining the Engine AIR CleanerCleaning the Foam Precleaner Spark Arrestor Muffler Clean AIR Intake ScreenChecking the Engine Spark Plug Battery Maintenance Cleaning the GeneratorWeekly Every SIX MonthsDrive Belt OUT of Service ProcedureExercising the Generator Wattage Reference GuidePrimepact 66G and 66LP Recreational Vehicle Generators Part General Hazards Electrical Hazards Standards Booklets Purpose and Scope Installation InstructionsEquipment Description Generator Engine Operating SpeedMajor Features and Dimensions Generator Support Location and SupportGenerator Location Suspended MountingGenerator Restraint Generator CompartmentsCompartment Construction Compartment SizeAcoustics Sound Insulating MaterialsCompartment Floor Cutout Compartment Floor Cutouts Cooling and Ventilating AIRCooling AIR Inlet Openings Generator AirflowCompensating for Restrictions Testing the InstallationGasoline Fuel System Parts not Included in Fuel System LP GAS Fuel SystemGenerator Fuel Supply Line Some Important Considerations Primary RegulatorVapor Withdrawal Gaseous CarburetionFuel Supply Lines Exhaust SystemExcess Flow Valve Leakage TestsWiring Exhaust System SafetyElectrical Connections Type of Exhaust SystemBattery Installation 18 Transfer Switch Isolation Method Battery CablesBattery Cable Connections Optional AccessoriesBattery Compartment Remote Panel ModelsTesting Under Load Post Installation TestsBefore Initial START-UP Initial StartInstallation Checklist Problem Cause Correction Troubleshooting GuideGenerac Power Systems, Inc Electrical Data Exploded Views and Parts Lists QTY Description To Engine BASE, Mounting To Engine BASE, Mounting To Engine Ground Item Part NO. QTY. Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists Carburetor Assemby CARB. V-TWIN L/P Primepact 66G and 66LP Recreational Vehicle Generators Primepact 66G and 66LP Recreational Vehicle Generators Primepact 66G and 66LP Recreational Vehicle Generators PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyGenerac Power SYSTEMS, INC