Installing a D3LX CO Module in an LEC | |
|
|
Fiber patch cord
Fiber clip
D3LX CO
Figure 7. Installing the D3LX CO
9After removing the protective cover from a fiber patch cord, clean the
POWER VERIFICATION
Verification of Electrical DS3 Power Level
1Apply power to the D3LX CO.
2Attach the fiber patch cord from the D3LX CO to a meter.
3Confirm that the readings are within the specification
If the reading is not within the specification, check all
4Once the readings are within specification, disconnect the patch cord from the meter. Now that the DS3 power level meets optical specifications, verify the D3LX CO module.
12 | August 30, 2002 | D3LX CO and RMT Modules |