The performance of a fiber-optic system is mainly dependent on the fiber-optic connector cleaning procedures performed before installation. Clean all connectors and adapters before making any connections.

CLEANING

1Assemble the required cleaning materials shown in Figure 24:

Lint-free laboratory wipes

Cotton tipped swabs

Isopropyl alcohol in a pressurized dispenser

Lint-free pipe cleaners

Clean, dry, oil-free compressed air

 

 

 

100

 

PIPE

 

 

U

DRSIX INCH

 

CLEANERS

MA

HLFLF

BK

 

ISO PR O PYL

SDLJF;LETHIEDF

 

HLFLF

 

AL CO HO L

 

 

 

 

 

 

 

 

BKU

 

 

 

Q-Tips

PRO

 

 

 

 

 

 

 

M

 

 

SINGLE TIPPED

PLAISOPROPYLCOL

 

ASKLHF; SDA

 

 

 

 

 

 

 

KUL

 

 

KDL

 

 

 

 

 

 

APPLICATIONORS

 

 

 

 

MA HS

 

 

 

 

 

WLBBKUL

 

 

 

 

 

MA H

FFAH

 

 

 

 

FBOWL

 

 

 

 

 

 

SFF

OOBWBKBU H H

 

LFSL

BO

 

 

 

PIPE

 

 

MAHSSLF

 

KDLF;L

 

CLEANERS

 

 

OBWBKB UH H

MAH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIX INCH

Figure 24. Cleaning Materials

2Clean connectors as follows:

a Moisten a lint-free wipe with alcohol and then wipe completely around the connector ferrule twice; wipe several times across the tip.

bUse a lint-free dry wipe to wipe completely around the connector ferrule twice; wipe several times across the tip.

cBlow across the end of the ferrule with clean, dry, compressed air.

dVisually inspect the connector tip for cleanliness. If the tip does not appear to be thoroughly cleaned, repeat Step a through Step c.

3Clean adapters as follows:

a SC and FC adapters are cleaned by using a pipe cleaner moistened with alcohol. Insert the pipe cleaner into either end of the adapter and rotate so the inside surface of the adapter is wiped by the pipe cleaner. Repeat this procedure for the opposite end.

b Blow the adapter dry with clean compressed air.

4Clean attenuators with clean, dry compressed air only. Do not use a moistened wipe or pipe cleaner.