Local Configuration

LTPS-UM-8013-03

 

 

Press CTRL + A for assistance when making selections.

4Configure the fields as detailed in the Table 5 and assign the selections by pressing ENTER .

5Repeat Steps 2 through 5 for each D3LX system installed in the chassis.

Table 5. D3LX CO Configuration Fields–SCU V3.7 or later

Field Name

Type

Options

Description

Default

 

 

 

 

 

Unit Equip State

Toggle

EQUIPPED

Establishes communication with SCU. Module

UNEQUIPPED

 

 

 

must be set to EQUIPPED before remaining

 

 

 

 

selections are allowed.

 

 

 

 

 

 

 

 

UNEQUIPPED

No communication with SCU.

 

 

 

 

 

 

Unit Service State

Toggle

IN SERVICE

Places the unit in service and allows equipment

OOS

 

 

 

alarm reporting by the SCU. Must be set to IS

 

 

 

 

for reporting of equipment alarms.

 

 

 

 

 

 

 

 

OUT OF SERVICE

Removes unit from service and stops

 

 

 

 

equipment alarm reporting by the SCU.

 

 

 

 

 

 

Unit Protect State

Toggle

PROTECTED

Line protection

Unprotected

 

 

 

 

 

 

 

UNPROTECTED

No protection

 

 

 

 

 

 

Optical Service State

Toggle

IN SERVICE

Places facility in service and enables T2 alarm

OOS

 

 

 

reporting by the D3LX CO.

 

 

 

 

 

 

 

 

OUT OF SERVICE

Removes facility from service and stops T2

 

 

 

 

alarm reporting by the D3LX CO.

 

Optical BER Alarm

Toggle

Set to OFF or set

Threshold

 

between 10-6and 10-10

The average Bit Error Ratios of both the

10-8

incoming optical signals are monitored by the D3LX CO. By monitoring BERs, the D3LX CO is capable of triggering a minor alarm when any of the monitored signals degrades below the BER threshold level.

Optical BER Switch

Toggle

Range from 10-4to

Sets the threshold at which the APS will be

10-6

Threshold

 

10-10

executed.

 

DS3 Provisioned

Toggle

YES

Brings up T1 default settings and allows

NO

(set for each T1)

 

 

configuration changes.

 

 

 

 

 

 

 

 

 

 

 

 

NO

No configuration changes allowed.

 

 

 

 

 

 

DS3 Service State

Toggle

IN SERVICE

Select IS after completing the remaining con-

OOS

 

 

 

figurations.

 

 

 

 

 

 

 

 

OUT OF SERVICE

Leave this field at OUT OF SERVICE (versus IN

 

 

 

 

SERVICE) at this time to avoid undesirable

 

 

 

 

reporting of alarms.

 

 

 

 

 

 

DS3 Transmit LBO

Toggle

0–225 ft., 226–450 ft.

The DS1 signal output provides standard DSX

0–225 ft.

Local

 

 

signal levels which can be compensated for at

 

 

 

 

various distances, such as cable length.

 

 

 

 

 

 

DS3 Transmit LBO

Toggle

0–225 ft., 226–450 ft.

The DS1 signal output provides standard DSX

0–225 ft.

Remote

 

 

signal levels which can be compensated for at

 

 

 

 

various distances, such as cable length.

 

Continued

24

August 30, 2002

D3LX CO and RMT Modules