Local Configuration | |
|
|
LOCAL CONFIGURATION
A D3LX system can be configured locally by an SCU (version 3.7 or later) with a D3LX CO module in an LEC. It can also be configured remotely by a D3RCAM with a D3LX RMT module installed in a remote chassis. See “Remote Configuration” on page 33 for the procedure configuring remotely using the D3RCAM.
The following details the local configuration procedure.
CONFIGURING THE D3LX SYSTEM THROUGH THE SCU
Use the craft interface system menu to view or edit the configuration for each D3LX module in the chassis. This menu can also be used to equip, provision, assign thresholds, and assign service state.
3.Unit Configuration
4.D3LX Configuration
1Connect a maintenance terminal to the craft port on the SCU front panel and log on to the craft interface system as described in “Connecting a Maintenance Terminal to the SCU Craft Port” on page 19.
See “Navigating Through Craft Interface Menus” on page 22 for detailed information on making selections.
2From the Main menu, select 3. Unit Configuration.
3From the Unit Configuration menu, select 4. D3LX Configuration. The D3LX Configuration appears as shown in Figure 13.
Figure 13. D3LX Configuration Screen
D3LX CO and RMT Modules | August 30, 2002 | 23 |