Making detailed settings to the central control unit, add-on control unit(s) or room sub control unit(s)

NOTE:

Make the settings to the central control unit, add-on control unit(s) or room sub control unit(s) respectively. You cannot select multiple control units at the same time.

The following setting item buttons are displayed in the “Advanced settings” window.

F (central control unit only)

G

*Click either the button F or G to open the corresponding setting window, and then make the settings in the displayed window(s). See the detailed

instructions for F or G below.

*Click Close to close the current window and return to the previous window.

FSettings on [Contact input] window (for central control unit only)

Set the input method to each of the CONTACT INPUT terminals.

1Select the input terminal from S1 to S4 from the pull- down menu.

2[Contact type]:

Select either Normally open (NO) or Normally closed (NC).

3[Trigger condition]:

Select [None], [Broadcast chime] or [Stop chime] as the trigger condition. When an input is detected, the selected action is triggered.

[None]:

None will be triggered if an input is detected.

[Broadcast chime]:

Chime paging to the designated zone is triggered if an input is detected.

[Stop chime]:

The currently-transmitted chime is stopped if an input is detected.

*Only when [Broadcast chime] is selected, the following items are valid.

[Sound source]:

Select either [Internal sound source] or [External sound source] as the source of chime. When [Internal sound source] is selected, select a sound file or sequence from the registered ones in the list.

(You need to register sound files and/or sound sequences in advance. (→P. 17-18))

When [External sound source] is selected, select either “External sound source 1” or “External sound source 2”.

[Chime priority]:

Select the priority of chime paging from among “Normal”, “Priority” and “Urgent”.

[Zone name]:

Select the target zone of chime paging from the registered ones in the list.

4 Repeat step 1 to 3 to make the settings to other terminals.

5 Click Close to close the current window and return to the previous window.

GSettings on [Contact output] window

Set the trigger condition to each of the CONTACT OUTPUT terminals.

1 Select an output terminal from the pull-down menu.

*Select from L1 to L8 for the central control unit, and select from L1 to L4 for the add-on control unit and room sub control unit.

2 [Contact type]:

Select either Normally open (NO) or Normally closed (NC).

3 [Trigger condition]:

Select the action as the trigger condition from among the following. When the selected action is detected, output is triggered.

[None]:

No output will be triggered.

[Calling notice]:

Set ON or OFF for “Normal”, “Priority” or “Urgent”.

[Door release]:

Select one of the registered sub stations in the list to which an electric door strike is connected. (Click Reference , and then select the target station.)

[External sound source] (central control unit only): Select either “External sound source 1” or “External sound source 2” connected to the central control unit.

[PA output]:

Select from among “PA output 1” to “PA output 4” connected to the control unit.

4 Repeat step 1 to 3 to make the settings to other terminals.

5 Click Close to close the current window and return to the previous window.

16

Page 16
Image 16
Aiphone IS Series operation manual Settings on Contact output window, Select an output terminal from the pull-down menu