Installation

NOTE: The power cord (pigtail) is NOT supplied with the electric dryer. Type of pigtail and gauge of wire must conform to local codes and instructions.

The method of wiring the dryer is optional and subject to local code requirements.

POWER SUPPLY

POWER SUPPLY

1 2

NOTE: Connect the dryer to the power supply with the MAXIMUM RATED VOLTAGE listed on the nameplate.

A typical

INTERMEDIATE

30-Amp

FUSE BOX (May

Three-wire

be omitted if

Receptacle

service entrance

NEMA Type

box is fused)

10-30R

 

WALL RECEPTACLE

120 ± 12

120 ± 12

V.A.C.

V.A.C.

 

 

240 ± 12

 

V.A.C.

3

4

5 6

INTERMEDIATE SHUT-OFF (May be omitted if service entrance box is fused)

NOTE: Use COPPER WIRE only. k

 

L1 L2

7

L1 L2

 

 

 

Shorter than 15k (4.5 m) use 10 A.W.G.

PIGTAIL CONNECTION

 

DIRECT CONNECTION

 

Longer than 15k (4.5 m) use 8 A.W.G.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D816I

1

3-Wire Grounded Neutral 120/240 Volt, 60 Hertz

4

Metallic or Non-Metallic Sheathed Cable

 

AC 1 Phase Service Entrance Switch Box

 

 

(Copper wire only)

 

 

 

(See NOTE above)

 

5

Pigtail to Dryer (See NOTE above)

2

30 Ampere Fuses or Circuit Breaker

 

6

Neutral

 

 

3

Neutral Wire

 

7

Terminal Block in Dryer

 

 

Figure 17

26