If the gas service is not the same as that specified, DO NOT CONNECT THE GAS LINE TO THE TUMBLER! It will first be necessary to convert the gas burner orifices.

IMPORTANT: Any product revisions or conversions must be made by the Manufacturer’s Authorized Dealers, Distributors or local service personnel.

WARNING

To reduce the risk of fire or explosion:

The tumbler and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kPa).

The tumbler must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig (3.45 kPa).

W648

Installation Instructions

Purge air and sediment from the gas service line before connecting it loosely to the tumbler. Purge remaining air until odor of gas is detected, then tighten connection. Use pipe compound, resistant to actions of L.P. gas, on all pipe threads.

WARNING

Check all pipe connections, internal and external, for gas leaks using a soapy solution. To reduce the risk of explosion or fire, DO NOT USE AN OPEN FLAME TO CHECK FOR LEAKS! Gas connections should be checked annually for leakage.

W649