Installation Instructions
Gas Pipe Size Required For 1,000 Btu Natural Gas – 0.64 Specific Gravity at 7 ± 1.5 Inches (17.4 ± 4 mbar, 1.74 ± 0.37 kPa) Water Column Pressure
|
|
| Equivalent Length |
|
| ||
|
|
|
|
|
|
|
|
Gas | 25 feet | 50 feet | 75 feet | 100 feet |
| 125 feet | 150 feet |
Appliances | (7.63 m) | (15.25 m) | (22.88 m) | (30.50 m) |
| (38.13 m) | (45.75 m) |
Total | Based on 0.3 in Water Column Pressure Drop for Length Given | ||||||
Btu/hr. |
|
| Sizes shown in inches (mm) |
|
| ||
|
|
|
|
|
|
|
|
100,000 | 0.75 (19.05) | 0.75 (19.05) | 1 (25.40) | 1 (25.40) |
| 1 (25.40) | 1 (25.40) |
120,000 | 0.75 (19.05) | 1 (25.40) | 1 (25.40) | 1 (25.40) |
| 1 (25.40) | 1 (25.40) |
140,000 | 0.75 (19.05) | 1 (25.40) | 1 (25.40) | 1 (25.40) |
| 1 (25.40) | 1.25 (31.75) |
160,000 | 0.75 (19.05) | 1 (25.40) | 1 (25.40) | 1.25 (31.75) |
| 1.25 (31.75) | 1.25 (31.75) |
180,000 | 1 (25.40) | 1 (25.40) | 1 (25.40) | 1.25 (31.75) |
| 1.25 (31.75) | 1.25 (31.75) |
200,000 | 1 (25.40) | 1 (25.40) | 1.25 (31.75) | 1.25 (31.75) |
| 1.25 (31.75) | 1.5 (38.10) |
300,000 | 1 (25.40) | 1.25 (31.75) | 1.25 (31.75) | 1.5 (38.10) |
| 1.5 (38.10) | 1.5 (38.10) |
400,000 | 1.25 (31.75) | 1.25 (31.75) | 1.5 (38.10) | 1.5 (38.10) |
| 1.5 (38.10) | 2 (50.80) |
500,000 | 1.25 (31.75) | 1.5 (38.10) | 1.5 (38.10) | 2 (50.80) |
| 2 (50.80) | 2 (50.80) |
600,000 | 1.5 (38.10) | 1.5 (38.10) | 2 (50.80) | 2 (50.80) |
| 2 (50.80) | 2 (50.80) |
700,000 | 1.5 (38.10) | 2 (50.80) | 2 (50.80) | 2 (50.80) |
| 2 (50.80) | 2.5 (63.50) |
800,000 | 1.5 (38.10) | 2 (50.80) | 2 (50.80) | 2 (50.80) |
| 2.5 (63.50) | 2.5 (63.50) |
900,000 | 2 (50.80) | 2 (50.80) | 2 (50.80) | 2.5 (63.50) |
| 2.5 (63.50) | 2.5 (63.50) |
1,000,000 | 2 (50.80) | 2 (50.80) | 2 (50.80) | 2.5 (63.50) |
| 2.5 (63.50) | 2.5 (63.50) |
1,100,000 | 2 (50.80) | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) |
| 2.5 (63.50) | 2.5 (63.50) |
1,200,000 | 2 (50.80) | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) |
| 2.5 (63.50) | 2.5 (63.50) |
1,300,000 | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) | 2.5 (63.50) |
| 2.5 (63.50) | 3 (76.20) |
1,400,000 | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) | 2.5 (63.50) |
| 3 (76.20) | 3 (76.20) |
1,500,000 | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) | 2.5 (63.50) |
| 3 (76.20) | 3 (76.20) |
1,600,000 | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) | 3 (76.20) |
| 3 (76.20) | 3 (76.20) |
1,700,000 | 2 (50.80) | 2.5 (63.50) | 2.5 (63.50) | 3 (76.20) |
| 3 (76.20) | 3 (76.20) |
1,800,000 | 2.5 (63.50) | 2.5 (63.50) | 3 (76.20) | 3 (76.20) |
| 3 (76.20) | 3 (76.20) |
1,900,000 | 2.5 (63.50) | 2.5 (63.50) | 3 (76.20) | 3 (76.20) |
| 3 (76.20) | 3 (76.20) |
2,000,000 | 2.5 (63.50) | 2.5 (63.50) | 3 (76.20) | 3 (76.20) |
| 3 (76.20) | 3.5 (88.90) |
2,200,000 | 2.5 (63.50) | 3 (76.20) | 3 (76.20) | 3 (76.20) |
| 3.5 (88.90) | 3.5 (88.90) |
2,400,000 | 2.5 (63.50) | 3 (76.20) | 3 (76.20) | 3 (76.20) |
| 3.5 (88.90) | 3.5 (88.90) |
2,600,000 | 2.5 (63.50) | 3 (76.20) | 3 (76.20) | 3.5 (88.90) |
| 3.5 (88.90) | 3.5 (88.90) |
2,800,000 | 2.5 (63.50) | 3 (76.20) | 3 (76.20) | 3.5 (88.90) |
| 3.5 (88.90) | 3.5 (88.90) |
3,000,000 | 2.5 (63.50) | 3 (76.20) | 3.5 (88.90) | 3.5 (88.90) |
| 3.5 (88.90) | 4 (101.60) |
|
|
|
|
|
|
|
|
For L. P. Gas, correct the total Btu/hr. by multiplying it by 0.6. The answer is the equivalent Btu on the above chart.
The installation must conform with local codes or, in the absence of local codes:
•with the latest edition of the “National Fuel Gas Code,” ANSI Z223.1/NFPA 54 in the U.S.A.,
•with•and Australian Gas Association/Australian L.P. Gas Association requirements in Australia.
Figure 7
20 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | M412060 |