Installation Instructions

Gas Requirements (continued)

EXAMPLE:Gas Furnace

Gas

Meter

IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers connected to single gas service. Other gas using appliances should be connected upstream from loop.

Gas

 

Water

Gas Space

Heaters

Heaters

 

 

Tumblers

 

Gas Shut-Off

 

Valves

 

Gas

 

Line

 

Pressure

 

Tap

IMPORTANT: Line pressure must be maintained at 6-1/2 ± 1-1/2 water column inches for Natural Gas (10 ± 1-1/2 water column inches for L.P. Gas)

with all gas appliances running (tumblers, water heaters, space heaters, furnace, etc.).

An in-line pressure regulator may be required on Natural Gas models if the line pressure exceeds eight water column inches pressure with all gas appliances firing.

NOTE: Minimum pipe size to tumbler is 1/2 inch (1.27 cm).

TMB2159N

Figure 8

Example Of Gas Supply Piping

Gas Furnace

(120,000 BTU/HR)

SAMPLE CALCULATIONS:

Equivalent Length = Total length of main gas supply pipe from the gas meter to the far end of the tumbler dryers

 

= 25 ft + 19 ft (7.62 meters + 5.79 meters)

 

= 44 ft (13.41 meters)

Total BTU/HR

=

The sum of the BTU/HR of all tumblers being

 

 

fed by the main gas supply pipe

 

=

18 x 75,000

 

=

1,350,000

Using the table in Figure 7, the main supply pipe diameter should be 2-1/2 in (6.35 cm).

Gas Water

 

Gas Tumbler

 

Dryer (75,000

Heaters

 

Gas Space Heaters

BTU/HR per

(400,000

(70,000 BTU/HR

cylinder)

BTU/HR each)

each)

 

 

 

Gas

Meter

25 ft (7.62 meters)

Pressure

19 ft (5.79 meters)

 

Regulator

 

TMB2160N

Figure 9

M412060