Electrical Connection

Three-Wire Power Cord

WARNING

The dryer is grounded to neutral conductor at the terminal block. If local codes do not permit grounding through the neutral, proceed as shown on Four-Wire Connection instructions.

W174

To reduce the risk of electric shock, disconnect the electrical service to the dryer before proceeding.

W135

1.Remove the screw and terminal block access cover from the rear of the dryer cabinet.

2.Insert ends of direct wire through power supply hole (containing proper strain relief) in rear of dryer cabinet. Refer to Figure 26. Connect the power cord, or direct wiring, to the appropriate terminal block terminals using the three wire- binding screws from the accessories bag in the envelope shipped inside the dryer cylinder. If the dryer had previously been connected with a four-wire power cord, remove the four-wire power cord by reversing procedures under Four-Wire Power Cord instructions.

Installation

IMPORTANT: Use only a U.L. listed No. 10 A.W.G. (copper wire only) three conductor power supply cord kit rated 240 Volts (minimum) 30 Amperes and labeled as suitable for use in a clothes dryer.

3. Tighten these wire-binding screws firmly.

IMPORTANT: Failure to tighten these screws firmly may result in wire failure at the terminal block.

4.Secure the strain relief to the power cord, or wires, where they enter the dryer cabinet.

5.Check the continuity of the ground connection before plugging the cord into an outlet. Use an acceptable indicating device connected to the center grounding pin of the plug and the ground screw on the back of the cabinet.

6.Reinstall access cover and screw.

1

 

 

 

2

 

 

 

D607I

 

 

3

 

 

 

 

D607I

1

Grounding Pin

3

Indicating Device (Must show continuity)

2Ground Screw on Back of Cabinet

Figure 25

801539