Installation

5

1

A B C D E F G H I J K

2

3

30°

1

2

AIR

FLOW

4

EXHAUST AIR FLOW

MAXIMUM LENGTH OF DUCT

30 feet (9.1 m)

 

 

 

EXHAUST

HORIZONTAL EXHAUST INSTALLATION

OUTLET

 

 

 

H318I

NOTE: Where the exhaust duct pierces a

3

2 in. (5 cm) Minimum or Clearance per Local

combustible wall or ceiling, the opening must be

 

Codes

 

sized per local codes.

4

No Screen or Cap

 

Wall

5

Clean Out Cover – Inspect Monthly

Figure 40

1

WARNING

To reduce the risk of fire and the accumulation of combustion gases, DO NOT

2

3

exhaust dryer air into a window well, gas vent, chimney or enclosed, unventilated area, such as an attic, wall, ceiling, crawl space under a building or concealed space of a building.

W045

CONNECT TO DRYER

5

4

 

VERTICAL EXHAUST INSTALLATION

H319I

1No Screen or Cap

2Roof

3Wall

42 in. (5 cm) Minimum or Clearance Per Local Codes

5NOTE: Where the exhaust duct pierces a combustible wall or ceiling, an opening must be sized as shown or per local codes.

Figure 41

Duct

Minimum Diameter of

Station

Collector Duct

 

 

A

4 inches (10.2 cm)

 

 

B

8 inches (20.3 cm)

 

 

C

9 inches (22.9 cm)

 

 

D

10 inches (25.4 cm)

 

 

E

11 inches (27.9 cm)

 

 

F

12 inches (30.5 cm)

 

 

G

13 inches (32.6 cm)

 

 

H

14 inches (35.6 cm)

 

 

I

15 inches (38.1 cm)

 

 

J

15 inches (38.1 cm)

 

 

K

16 inches (40.6 cm)

 

 