Exhaust Requirements
WARNING
A drying tumbler produces combustible lint. To reduce the risk of fire, the tumbler must be exhausted to the outdoors.
W057
To reduce the risk of fire and accumulation of combustible gases, DO NOT exhaust tumbler air into a window well, gas vent, chimney or enclosed, unventilated area such as an attic wall, ceiling, crawl space under a building, or concealed space of a building.
W059
Layout
Whenever possible, install tumblers along an outside wall where duct length can be kept to a minimum, and
Make-Up Air
A tumbler is forced air exhausted and requires provisions for
IMPORTANT: Do not obstruct the flow of combustion and ventilation air.
The required
220 square inches (1418 sq. cm) for T30 models
288 square inches (1856 sq. cm) for T45 models
Venting
WARNING
To reduce the risk of fire due to increased static pressure, do not install
W730
IMPORTANT: Installing
For maximum efficiency and minimum lint accumulation, tumbler air must be exhausted to the outdoors by the shortest possible route.
Proper sized exhaust ducts are essential for proper operation. All elbows should be sweep type. Exhaust ducts must be assembled so the interior surfaces are smooth, so the joints do not permit the accumulation of lint. DO NOT use plastic or thin foil flexible ducts. Use exhaust ducts made of sheet metal or other non- combustible material. Use duct tape or
Verify that old ducts are thoroughly cleaned out before installing new tumbler(s).
WARNING
Improperly sized or assembled ductwork causes excess back pressure which results in slow drying, lint collecting in the duct, lint blowing back into the room, and increased fire hazard.
W355
NOTE: Exhaust ducts must be constructed of sheet metal or other noncombustible material. Such ducts must be equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel not less than 0.0195 inches (0.495 mm) thick. Local codes may require additional thickness.
Where the exhaust duct pierces a combustible wall or ceiling the opening must be sized per local codes. The space around the duct may be sealed with