Electrical Requirements
Electrical Requirements for Gas and Steam Models
Refer to Table 10 and Table 11.
NOTE: Minimum wire sizes are obtained from Canadian Electrical Code for 75°C Conductors and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.
For T30 Gas and Steam Models
(For Total Machine):
NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.
NOTE: Use copper conductors only.
NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).
| Terminal Block |
| Recommended |
| Recommended | |
Serial Plate | Current | Fuse or | Breaker | Minimum | ||
Connections | ||||||
Voltage | (Amps) | Breaker Rating | Poles | Conductor Size | ||
Required | ||||||
|
| (Amps) |
| [AWG (mm2)] | ||
120V/60 Hz/1ph | L1, Neutral, | 16.0 | 20 | 1 | 12 (3.31) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, Neutral, | 8.0 | 10 | 2 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
100V/60Hz/1ph | L1, Neutral, | 22.0 | 30 | 1 | 10 (5.26) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, Neutral, | 11.6 | 15 | 1 | 14 (2.08) | ||
1ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
100V/50Hz/1ph | L1, Neutral, | 24.2 | 35 | 1 | 8 (8.37) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
200V/50Hz/1ph | L1, Neutral, | 15.0 | 20 | 1 | 12 (3.31) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, Neutral, | 15.0 | 20 | 1 | 12 (3.31) | ||
1ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
L1, L2, L3, | 6.4 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
240V/60Hz/3ph | L1, L2, L3, | 6.4 | 10* | 3 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
200V/50Hz/3ph | L1, L2, L3, | 5.8 | 10* | 3 | 14 (2.08) | |
and ground |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
L1, L2, L3, | 7.0 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
380V/50 or 60Hz/ | L1, L2, L3, | 3.0 | 10* | 3 | 14 (2.08) | |
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
L1, L2, L3, | 3.2 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
| |
L1, L2, L3, | 3.3 | 10* | 3 | 14 (2.08) | ||
3ph | and ground |
|
|
|
| |
|
|
|
|
|
|
*3 Phase machines should not have fuses, breakers only.
Table 10
40 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 70304601 |