Installation 26
TILT MODELS
Electrical conductors must be flexible and capable of accommodatingthe washer movements during
the loading and unloading operations and secured at their ends.
The connection of the external dosing electrical signals takes
place on the terminals of A4 and A6 boards, located at the
lower part of the washer electrical box (fig. 21).
If you use dosing signals coming from A-4 and A-6 board,
you must link the COM terminal of each board (X6-1 and X3-
1) by means of an electric insulation conductor of 0.75mm2
and 400V.
Remove protection cover A of the connection box.
Insert the conductor in Ed and secure it with the fixing
device.
Remove protection cover B of the electric panel.
Pass the conductor through the cable ducting C
Once the conductor connection is done, REPLACE AND
LOCK THE COVERS CORRECTLY.
fig. 21
POTENTIAL FREE RELAY CONTACTS
Use of four dosing signals.
The dosing signals from 1 to 4 are originated in A4 board.
Connect the common dosing cable to the terminal identified
as COM.
Connect the cables between the washer and the dosing
unit to A4 board in the order indicated in the table in
section 3.6.2. (fig. 22).
IMPORTANT
This connection allows for the maximum strength at
each of the 1A outputs.
Dosing signals ARE NOT PROTECTED by the washer
fuses.
fig. 22