Installation
Water ConnectionUW 2 Speed Pocket Hardmount
Water Supply Information
Water inlet connection size, in. (mm) |
| 3/4 (19) | |
|
|
| |
Number of water inlets (standard) |
| 4* | |
|
|
| |
Recommended pressure psi (bar) |
| 30 – 85 | |
|
|
| (2 – 5.7) |
|
|
| |
Inlet flow capacity, gal/min |
| 35 | 28 (106) |
(l/min) (80 psi) |
|
|
|
| 60 | 39 (148) | |
|
| ||
|
|
|
|
*M and B models have two connections.
Table 6
Connections should be supplied by hot and cold water lines of at least the sizes shown in Table 7. Installation of additional machines will require proportionately larger water lines. Refer to Table 7.
To connect water service to machine with rubber hoses, use the following procedure:
1.Before installing hoses, flush the water system for at least two minutes.
2.Check filters in the
3.Hang the hoses in a large loop; do not allow them to kink.
If additional hose lengths are needed, use flexible hoses with screen filters. Each hose should have a screen filter installed to keep rust and other foreign particles out of the water inlet valves.
Pressure of
UW 2 Speed Pocket Hardmount
Water Supply Line Sizing
| Number of | Supply Line Size | ||
|
| in. (mm) | ||
| Machines |
|
|
|
| Main |
| Hot/Cold | |
|
|
| ||
|
|
|
|
|
| 1 | 1 (25) |
| 3/4 (19) |
|
|
|
|
|
35 | 2 |
| 1 (25) | |
|
|
|
| |
3 | 2 (50) |
| ||
|
| |||
|
|
|
|
|
| 4 | 2 (50) |
| |
|
|
|
|
|
| 1 |
| 1 (25) | |
|
|
|
|
|
60 | 2 | 2 (50) |
| |
|
|
|
| |
3 | 2 (50) |
| ||
|
| |||
|
|
|
|
|
| 4 |
| 2 (50) | |
|
|
|
|
|
Table 7
Suitable air cushions should be installed in supply lines to prevent “hammering.” Refer to .
1
2
PHM184N
P004I
1Air Cushions (Risers)
2Water Supply Faucets
Figure 11