I N S T A L L A T I O N
WATER VALVE
NOTE:
THE SHUT-OFF VALVE
MUST BE IN THE OPEN POSITION
WHEN THE OVEN IS BEING USED.
WATER DRAINAGE
The oven must discharge through an indirect waste pipe by means of an air gap. The drain fitting is supplied with a
Aunion is required. Install a
NOTE: In the U.S.A., this equipment is to be installed to comply with the Basic Plumbing Code of the Building Officials and Code Administrators International, Inc. [BOCA], and the Food Service Sanitation Manual of the Food & Drug Administration [FDA].
If several units are to be connected to one drain pipe, the dimensions of the pipe must be sufficient to allow an unobstructed water drain system.
back of oven
DRAIN CONNECTION
AIR GAP
2" (51mm); to be
within the first 12" (305mm) of oven drain
DRAIN
CONNECTION
NPT
AIR GAP
2" (51mm); to be
within the first 12" (305mm) of oven drain
WASTE PIPE
2" (51mm) Minimum NPT
diameter Manifold Pipe
*materials must withstand
temperatures up to 200°F (93° C)
diameter connection
required for drain
CT EXPRESS SERIES • INSTALLATION MANUAL •