The
dANGER
CONNECTING TO THE WRONG GASSUPPLY COULD RESULT IN FIRE OR
AN EXPLOSION CAUSING SEVEREINJURY AND PROPERTY DAMAGE.
installation
gas specifications
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi. The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi.
NOTE: Customer/installer must provide manual gas
W A R N I N G
TO AVOID SERIOUS PERSONAL INJURY, installation of this appliance must conform to local, state, and national codes; the current edition of the American National Standard Z223.1, National Fuel Gas Code, and all local municipal building codes.
In Canada, installation must be in accordance with Standard CAN/CSA B 149.1 and Installation Codes - Gas Burning Appliances, and local codes.
Category I2H at 20 mbar for use in AT, DK, FI, IE, IT, PT, SE, CH.
Category I2E(20) at 20/25 mbar for use in DE, LU.
Category I2E+(20/25) at 20/25 mbar for use in BE, FR.
Category I2L(25) at 25 mbar for use in NL.
Category
Category I3B/P(30) at 30 mbar for use in DK, FI, NL, SE.
Category I3B/P(50) at 50 mbar for use in AT, DE, CH.
Category I3P(37) at 37 mbar for use in FI, DE, IE, CH.
declared input (kw) | 35.15 |
|
gas group | I2H(20), I2E(20), I2E+(20/25), I2L(25), | |
| I3B/P(30), I3B/P(37), I3B/P(50), I3P(37), | I3P(50) |
inlet pressure (mbar) | 17.5 (NAT) and 27.5 (LP) |
|
declared setting pressure at the | 12.5 (NAT) and 25 (LP) |
|
outlet from the gas valve (mbar) |
|
|
main burner type | Infrared type with blower and venturi valve | |
number of injectors | 1 |
|
main injector type | N/A |
|
main injector size and markings | N/A |
|
main burner aeration opening | Variable |
|
size |
|
|
ignition | Direct spark electronic ignition |
|
inlet connection | 20.995 mm male thread |
|
GAS PRESSURE CHART
The fryer has been factory adjusted according to the gas type specified on the fryer identification name plate.
GAS FRYER TECHNICAL SPECIFICATIONS
Natural Gas
Min. Connected Pressure | 5.0" W.C. |
| 1.2 kPa | |
Max. Connected Pressure | 11.0" W.C. |
| 2.74 kPa | |
Gas Consumption | 120 CFM |
| ||
Gross Thermal Output | 120,000 Btu/hr | |||
Propane Gas |
|
|
|
|
|
|
|
| |
|
|
|
| |
Min. Connected Pressure | 10.0" W.C. |
| 2.5 kPa | |
Max. Connected Pressure | 14.0" W.C. |
| 3.5 kPa | |
Gas Consumption | 48 CFM |
| ||
Gross Thermal Output | 120,000 Btu/hr | |||
|
|
|
|
|
INSTALLATION REqUIREMENTS
gaS COnneCTiOn: 1/2" NPT
hOOd inSTallaTiOn iS reQuired
Check plumbing codes for proper supply line sizing to attain minimum burner manifold pressure shown:
NATURAL GAS: 5.0" W.C. | PROPANE GAS: 10.0" W.C. |
(1.2 kPa) | (2.5 kPa) |
MAX. RECOMMENDED
INLET PRESSURE: 11" W.C (2.74 kPa)14" W.C. (3.5 kPa) nOTe: If a flexible gas line is used, it must be AGA
approved, commercial type and at least 1/2" I.D.
Manual gas
NOT FACTORY SUPPLIED