•If arcing does not occur:
•Check circuitry; refer to
•Check transformer
•Check spark igniter in burner
•Refer to the
•Retest
5b) To check the electrical actuation of the motorized gas valve:
•Shut the main gas valve to the dryer.
•Open the disconnect block on
NOTE: REMOVING THE VOLTAGE AT ANY TIME WILL CLOSE THE VALVES INSTANTLY.
•If valves operate properly, close disconnect on
•If the valves do not open correctly;
•Check circuitry; refer to
•Check motorized valves
•Refer to Section VI, Part D, Gas Burner and Ignition System on page 37 thru page 45.
•Retest
6b) To verify that MS4 AUX is operational:
Start a drying cycle, MS4 contactor should pull in, and start the LINT FAN and LINT SCREEN motors. Simultaneously MS4 AUZ1 should close, enabling MS8 Coil (Burner Fan Motor) to be asserted by burner controller module. Does MS4 pull in?
•If MS4 pulls in go to paragraph #7b
•If MS4 “DOES NOT” pull in;
•Check that PLC (Programmable Logic Controller) OUTPUT 3 L.E.D. (light emitting diode) is “ON”
•Check that fuse #14 L.E.D. (light emitting diode) “IS NOT” lit