4.Lint Chamber Pressure Switch - PS3
The “Lint Chamber Pressure Sensing Switch” is located on the left rear side of the
5.Tumbler (Basket) Tilt Problems “LEVEL FAULT”
A “LEVEL FAULT” message is generated by the incorrect state of either the FRONT or REAR sensor switches. The following information will address the “LEVEL” signals, since they are associated with the Base Electrical Junction Box.
a)PROBABLE CAUSES;
1a) Wiring back to the PLC (Programmable Logic Controller)
b)PROBABLE SOLUTIONS;
1b) For a quick check of the FRONT DOWN and REAR DOWN signals to the PLC (Programmable Logic Controller) perform the following:
FRONT DOWN signal test procedure: paragraph 5a above
REAR DOWN signal test procedure: paragraph 5b above
2b) Place the
•Actuate the Front Down switch by hand.
•Have someone verify that PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #11 lights when the switch actuator is down, and is OFF when the actuator is up.
•Does L.E.D. (light emitting diode) #11 come “ON” when the switch is down?
•If yes, wiring is OK.
•Check switch and actuator placement and tilt actuation.
NOTE: If actuator is at a 90° or greater angle with the base, the actuator will damage if machine is lowered.
83