•STOP DETECTOR RELAY CONTACT SMD NO
This relay contact is used as an interlock to shut down the burner in the event that the tumbler (basket) has stopped for more than
•FLAME DETECTOR PROBE
This device is part of the
•BURNER CHASSIS GROUND
This signal is derived for a wire attached directly to the Burner Chassis and through the Solenoid Junction Box and terminated on the S2 of the Burner Controller.
2.Output Signal Component Description
•PILOT GAS VALVE V1
This 110 VAC electrically activated valve is located on the lower left of the Burner Section. Its wires are terminated in the Solenoid Junction Box, and activated by a signal derived from Pin #3 of the Burner Controller.
•IGNITION TRANSFORMER T3
This transformer is located on the left side of the Burner Section. Its primary is terminated in the Solenoid Junction Box is connected to Pin #4 of the Burner Controller. Its secondary is connected to a spark igniter in the burner.
•MOTORIZED GAS VALVES V3 and V2
These 110 VAC motorized valves are located on the left side of the Burner Section, and are controlled by a signal from the Burner Controller Pin #5. Their connections are terminated in the Solenoid Box.
•BURNER FAN CONTROL
This 110 VAC output of PIN #8 of the Burner Controller is used to enable the Coil of MS8, a motor starter for the Burner Combustion Fan. MS4 AUX is used to insure that the lint fan and lint screen motors are powered prior to enabling MS8.
•“RED” INDICATOR LIGHT
Attached to the left side of the base of the burner controller is a “RED” indicator light. This indicator indicates the burner controller has power.