IMPORTANT: Even though a minimum of only 12 inches is required, 18 inches or more is suggested, especially in cases where sprinkler heads are over the installation and service.
IMPORTANT: When fire sprinkler systems are located above the dryers, a minium of 18 inches above the dryer console (module) is required. Dryers may be positioned side wall to side wall however, a 1/16” minimum allowance is required between dryers (or wall) for base of installation and maintenance. Allowances must be made for the opening and closings of the control door and the lint door.
D. MAKE UP AIR REQUIREMENTS
When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the
Air supply