17
Bad Coin Lockout Status (bCLO)
In this program status, the computer counts in milliseconds the amount of time required for a coin entry signal. If
someone should tamper with the coin acceptor or attempt to insert a foreign object, the Phase 3 microprocessor
controller (computer) will lock up, shut the dryer down, and the display will read “OFF.” This condition will be
evident, even if coins are inserted, until the program is manually reset by closing and reopening the program
switch (PS).
Bad Coin Reset (bCrS)
When set in this program (“bCrS”), the Phase 3 microprocessor controller (computer) counts in milliseconds the
amount of time required for a coin entry signal. If someone should tamper with the coin acceptor or attempt to
insert a foreign object, the Phase 3 microprocessor controller (computer) will not accept the entry and will
automatically reset itself immediately for the next entry.
Accumulative Time (AtIn)Single Coin
In this program mode (“AtIn”), each coin inserted has a specific value in time, which is determined by the “Time
Per Left Coin” (“tPLC”) program (PL11).
Example No. 1:If the dryer is equipped with a 25¢ coin acceptor and the desired time is 12 minutes, each
additional coin inserted would yield 12 minutes.
Settings: PL09 (LCdE)............ 25
PL11 (tPLC) .............12
PL12 (AtSt)............... 25
Example No. 2:If the dryer is equipped with a 25¢ coin acceptor and the “Amount To Start” (“AtSt”) is 50¢
for 30 minutes, the insertion of each additional coin would yield 15 minutes. In this application
the “Time Per Left Coin” (“tPLC”) is determined by dividing the “Total Vend Time” (30) by
the “Amount To Start” (“AtSt”) (i.e. 50¢) and then, multiplying by the Left Coin Denomination
(“LCdE”).
Formula: (Total Vend Time/AtSt)(LCdE) = tPLC
(30/50)(25) = 15 minutes
Settings: PL09 (LCdE)............ 25
PL11 (tPLC) .............15
PL12 (AtSt)............... 50