American Power Conversion 10-30 KVA, 200/208 V manual Operation Display Messages/Troubleshooting

Models: 10-30 KVA 200/208 V

1 52
Download 52 pages 5.68 Kb
Page 24
Image 24

Operation – Display Messages/Troubleshooting

Display Message

Meaning

Corrective Action

 

 

 

Low-Battery.

The UPS is in battery operation and

Shut down the system and the load

 

the battery charge is low.

equipment or restore incoming volt-

 

Note: Runtime is limited in duration.

age.

 

 

 

Load Is No Longer

The load previously exceeded the

No is corrective action necessary.

Above Alarm Threshold.

alarm threshold and the situation has

 

 

been corrected either because the load

 

 

decreased or the threshold was

 

 

increased.

 

 

 

 

Load Power Is Above

The load has exceeded the user-

Option 1: Use the display interface to

Alarm Limit.

specified load alarm threshold.

raise the alarm threshold.

 

 

Option 2: Reduce the load.

 

 

 

Mains Not Available.

The frequency or voltage is out of

Correct the input voltage to provide

Input Freq/Volt Out of

acceptable range for normal

acceptable voltage or frequency.

Range.

operation.

 

 

 

 

Min Runtime Restored.

The system runtime dropped below

No corrective action is necessary.

 

the configured minimum and has

 

 

been restored. Additional Battery

 

 

Modules were installed, the existing

 

 

Battery Modules were recharged, the

 

 

load was reduced, or the threshold

 

 

was decreased.

 

 

 

 

No Batteries Are

No battery power is available.

Check that batteries are inserted

Connected.

 

properly.

 

 

 

Number of Battery

One or more battery modules were

No corrective action is necessary.

Modules Decreased.

removed.

 

 

 

 

Number of Battery

One or more battery modules were

No corrective action is necessary.

Modules Increased.

added.

 

 

 

 

Replace Batt(s).

One or more Battery Modules need

Refer to the Module Replacement

 

replacement (only applicable with

section for procedures.

 

internal batteries).

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

Option 1: Allow the battery modules

Threshold.

the user-specified minimum runtime

to recharge.

 

alarm threshold. Either the battery

Option 2: If possible, increase the

 

capacity has decreased, or the load

number of battery modules.

 

has increased.

Option 3: Reduce the load.

 

 

Option 4: Decrease the alarm

 

 

threshold.

 

 

Contact APC Customer Support.

 

 

See back cover.

 

 

 

Site Wiring Fault.

Wrong phase rotation on the input

An electrician should check that the

 

side. The UPS will continue to supply

UPS has been wired properly.

 

conditioned power, but bypass is

 

 

unavailable.

 

 

 

 

16

Smart-UPS® VT 10-30kVA, 200/208V and XR Battery Enclosure Operation Guide 990-2359A

Page 24
Image 24
American Power Conversion 10-30 KVA, 200/208 V manual Operation Display Messages/Troubleshooting